EasyManua.ls Logo

RFL Electronics IMUX 2000 - Figure 2-2. Functional Diagram of Drop;Insert Section of M-DACS

Default Icon
982 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
M-DACS-T1 RFL Electronics Inc.
October 16, 2012 2-3 (973) 334-3100
2.2.3 DROP/INSERT FUNCTIONALITY
A drop/insert multiplexer is essentially a multiplexer configured as two back-to-back T1 Common
Modules (CM4s), in which some circuits terminate while others pass through. A drop/insert
multiplexer can terminate payload circuits from either of two different T1 circuits; that is, from either
of two different locations. (See Figure 2-2)
CHANNEL
MODULES
T1 CIRCUIT
FROM/TO
DACS MODULE
VOICE
MODULE
VOICE
MODULE
DATA
MODULE
DATA
MODULE
ORDERWIRE
MODULE
P A Y L O A D C I R C U I T S
CM4
CM4
T1 CIRCUIT
FROM/TO
DACS MODULE
Figure 2-2. Functional diagram of Drop/Insert section of M-DACS
2.2.4 POINT-TO-POINT SYSTEMS
The simplest type of IMUX 2000 M-DACS system configuration is a point-to-point system. A point-
to-point system consists of two M-DACS multiplexers connected by a single T1 electrical or fiber
optic circuit. (See Figure 2-3.) As the figure illustrates, the same payload circuits will appear at both
ends of a point-to-point system. Most payload types (such as voice and full-duplex data circuits) are bi-
directional, and will have both an input and an output at each multiplexer.
2.2.5 LINEAR DROP/INSERT SYSTEMS
The addition of one or more drop/insert multiplexers converts a simple point-to-point system into a
linear drop/insert system. (See Figure 2-4.) Data, voice, and orderwire (multiple drop voice) circuits
can be established between any two locations in a T1 linear drop/insert system. As shown in Figure 2-4,
a three-location system can provide circuits between Locations 1 and 2, Locations 2 and 3, and
Locations 1 and 3. The only limiting factor is the capacity of the T1 circuit between any two adjacent
locations, which is 24 time slots. Linear Drop/insert systems are not limited to a single drop/insert
multiplexer, and may contain more than three locations.

Table of Contents