EasyManua.ls Logo

RFL Electronics IMUX 2000 - Page 564

Default Icon
982 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL VF-5C RFL Electronics Inc.
October 8, 2012 36 (973) 334-3100
REMOTE CONTROL USING SCL COMMANDS
When installed in an IMUX 2000 remote controllable shelf, the RFL VF-5C module can be operated
under local or remote control. When under remote control, certain configuration parameters can only be
changed through the RS-232 remote port on the multiplexer. The remote interface for these modules
involves two codes: a “P” (parameter) code, and an “S” (status) code. See the IMUX 2000 instruction
manual for more information on the remote control interface.
The RFL VF-5C reports itself as a “Type 183” module.
“P” CODES
“P” codes, when used in the parameter field on a “SET” command, allow the user to set certain
parameters on the module by remote control, just like setting the switches on a module under local
control. “P” codes also appear in the response to a “CONFIG?” query, showing the current parameter
settings on the module.
There are thirteen “P” codes for the RFL VF-5C, P1 through P13. Each of these P codes can be a
decimal number from 0 to 255, which can also be represented as an eight-digit binary number (in
parenthesis). The binary representation is more useful for setting and interpreting the “P” codes, since
each binary digit (0 or 1) corresponds to the ON or OFF setting for a particular switch on the module.
Table 6 describes the meanings of the “P” codes for the RFL VF-5C.
A typical RFL VF-5C response to a “CONFIG?” query looks like this:
* OK
CHANNEL CARD 3, TYPE 183
UNDER REMOTE CONTROL
SVCE = ON
P01 = 3 (B00000011)
P02 = 3 (B00000011)
P03 = 28 (B00011100)
P04 = 28 (B00011100)
P05 = 1 (B00000001)
P06 = 1 (B00000001)
P07 = 28 (B00011100)
P08 = 28 (B00011100)
P09 = 1 (B00000001)
P10 = 1 (B00000001)
P11 = 1 (B00000001)
P12 = 0 (B00000000)
P13 = 0 (B00000000);

Table of Contents