Table 8. Remote configuration settings (“P” codes)
P Code Digit(s) And Switch Equivalent Value
(1)
Description
P01
B 0 0 0 0 0 0 0 0
- - - - - - -
0 Ch1 Loopback Disabled
CH1 LOOPBACK ENABLE
1 Ch1 Loopback Enabl
ed
B 0 0 0 0 0 0 0 0
- - - - - - -
0 C
h1 = DI-B
CH1 TX A DIR
1 Ch1 = Term
inal/DI-A
B 0 0 0 0 0 0 0 0
- - - - - - -
0 C
h1 Disabled
CH1 DISABLE
1 C
h1 Enabled
B 0 0 0 0 0 0 0 0
- - -
CH1 TIMESLOT
00001 t
o 11000
T1 Settin
gs
From left to right, these five bits represent the binary
value of the desired time slot from 1 through 24
in a T1 network. See Table 7 for a complete list of
these values.
00001 to 11111
E1 Settin
gs
From left to right, these five bits represent the binary
value of the desired time slot from 1 through 31
in an E1 network. See Table 7 for a complete list of
these values.
P02
B 0 0 0 0 0 0 0 0
- - - - - - -
0 Ch2 Loopback Disabled
CH2 LOOPBACK ENABLE
1 Ch2 Loopback Enabl
ed
B 0 0 0 0 0 0 0 0
- - - - - - -
0 C
h2 = DI-B
CH2 TX A DIR
1 Ch2 = Term
inal/DI-A
B 0 0 0 0 0 0 0 0
- - - - - - -
0 C
h2 Disabled
CH2 DISABLE
1 C
h2 Enabled
B 0 0 0 0 0 0 0 0
- - -
CH2 TIMESLOT
00001 t
o 11000
T1 Settin
gs
From left to right, these five bits represent the binary
value of the desired time slot from 1 through 24
in a T1 network. See Table 7 for a complete list of
these values.
00001 to 11111
E1 Settin
gs
From left to right, these five bits represent the binary
value of the desired time slot from 1 through 31
in an E1 network. See Table 7 for a complete list of
these values.
>> table continues on next page <<
1. These are the only legal values for setting parameters. Setting a parameter to a value outside its specified
range will produce unpredictable results.

Table of Contents