396 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 9 EtherNet/IP Communications
If the upload is not successful due to an E300 configuration trip, a display will
appear indicating that the profile will use default settings. Press OK to continue,
and press Cancel to abort the Module Discovery process. Read parameters 38 and
39 from the E300 Electronic Overload Relay to determine the reason for the
configuration trip. Fix the issue and repeat steps 1-5.
ATTENTION: If an Upload command is not successful during Module Discovery,
failure to cancel the Module Discovery process will result in the loss of any
preconfigured E300 Electronic Overload Relay configuration data. This
configuration data will not be retained and default values will be used when
adding an E300 Electronic Overload Relay online to a ControlLogix project.