Rockwell Automation Publication 193-UM015D-EN-P - February 2015 403
EtherNet/IP Communications Chapter 9
If the upload is not successful due to communication errors, a display will appear
indicating that there was an upload error, and the device profile will use its
existing settings. Press OK to continue. Identify and fix the reason for the
communication error and press Upload again, or press Cancel to remove any
module definition changes.
If the upload is not successful due to an E300 configuration trip, a display will
appear indicating that the profile will use its existing settings. Press OK to
continue. Read parameters 38 and 39 from the E300 Electronic Overload Relay
to determine the reason for the configuration trip. Fix the issue and press Upload
again, or press Cancel to remove any module definition changes.
ATTENTION: If an Upload command is not successful when manually adding an
E300 Electronic Overload Relay, failure to cancel the new module addition
process will result in the loss of any preconfigured E300 Electronic Overload
Relay configuration data. Default values will be used when the RSLogix 5000 or
Studio 5000 project is downloaded to the Logix controller or when adding an
E300 Electronic Overload Relay online to a ControlLogix project.