Motor control
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
4-13
• In addition to the status signals, the "QL..." lamp controls additionally
indicate the following:
– Unacknowledged fault (lamp output general fault QLS is flashing)
– Saving change-over command (QLE lamp outputs are flickering)
– Lamp test: All QL outputs are activated for approx. 2 s.
• Additional status information:
– Start active: If "Motor" is selected as the load type, this signal is present
during the start process of the motor for the duration of the specified
class time (e.g. 10 s for Class 10). Exceptions are the "Overload relay"
and "Solenoid valve" control functions.
– Interlocking time active: For control functions with a change in the
direction of rotation, the signal remains present until the specified
interlocking time has elapsed.
– Change-over pause active: For the "Dahlander", "Pole-changing starter"
and "Star-delta" control functions the signal is present until the specified
time has elapsed.
• Additional status information for the "Positioner" or "Solenoid valve" control
function:
– Feedback CLOSED (FC)
– Feedback OPEN (FO)
– Torque CLOSED (TC)
– Torque OPEN (TO).
These feedback signals specify the present status of the corresponding limit
switch and/or torque switch. The amount of usable status information is
directly dependent on the selected control function.
• Additional fault messages for the "Positioner" or "Solenoid valve" control
function:
– Stalled positioner: The torque switch has been activated before the
corresponding limit switch. The positioner may have stalled.
– Double 0: Both torque switches have been activated
– Double 1: Both limit switches have been activated
– End position: Positioner has left the end position without receiving a
control command
– Antivalence: The change-over contacts of the limit switch do not issue
an antivalent signal (only for the "Positioner 5" control function)

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals