Data formats and data records
SIMOCODE pro
B-34 GWA 4NEB 631 6050-22 DS 03
25.4 Signal conditioner 3 - Type Bit[2] 0, 1, 2, 3 0 0 = Non-
inverting
1 =
Inverting
2 = Edge rising
with memory
3 = Edge
falling with
memory
BU2
25.6 Signal conditioner 4 - Type Bit[2] 0, 1, 2, 3 0 BU2
26.0 Non-volatile
element 3 - Type
Bit[2] 0, 1, 2, 3 0 BU2
26.2 Non-volatile
element 4 - Type
Bit[2] 0, 1, 2, 3 0 BU2
26.4 Calculation module 2 - Operator Bit[2] 0, 1, 2, 3 0 0 = +,
1 = -,
2 =
*
,
3 = /
26.6 Reserved Bit[2] 0
27.0 Reserved Bit[2] 0
27.2 Reserved Bit[2] 0
27.4 Reserved Bit[2] 0
27.6 Reserved Bit[2] 0
28.0 Bit[4] - Parameters (25)
28.0 TM - sensor type Bit[3]
+Bit
000B - 100B 000B 000B = PT100,
001B = PT1000
010B = KTY83
011B = KTY84
100B = NTC
TM
28.4 Reserved Bit[4] 0
29.0 External fault 5 -
Reset also by
Bit[4] 0 - 1111B 0101B Bit[0] =
Panel reset,
Bit[1] =
Auto-reset,
Bit[2] =
Remote reset,
Bit[3] = OFF
command
reset
BU2
29.4 External fault 6 -
Reset also by
Bit[4] 0 - 1111B 0101B BU2
30.0 Reserved Bit[4] 0
30.4 Reserved Bit[4] 0
31.0 Reserved Bit[4] 0
31.4 Reserved Bit[4] 0
32.0 Truth table 7 type 2I/1O Bit[4] 0 .. 1111B 0 BU2
32.4 Truth table 8 type 2I/1O Bit[4] 0 .. 1111B 0 BU2
33.0 I
s
1 conversion factor - Denominator Bit[4] 0 .. 15 0 BU2
33.4 I
s
2 conversion factor - Denominator Bit[4] 0 .. 15 0 BU2
34.0 Hysteresis P - Cos phi - U Bit[4] 0 .. 15 5 1 % UM
34.4 Hysteresis for 0/4-20 mA Bit[4] 0 .. 15 5 1 % AM
35.0 Hysteresis free limits Bit[4] 0 .. 15 5 1 % BU2
35.4 Reserved Bit[4] 0
36.0 Byte parameters (29)
36.0 Reserved Byte 0
Byte.
Bit
Designation
(PRM group)
Type Range Unit De-
fault
Note Informa-
tion
Table B-14: Data record 132 - Extended device parameters 1 (Cont.)