Cabinet design and EMC
12.5 Connection system
SINAMICS S120 Combi
Manual, 11/2017, 6SL3097-4AV00-0BP7
285
Missing emergency motor shutdown option
If the motor holding brake is not connected or is incorrectly connected, serious physical
injuries can occur.
• Only connect motors with a safe electrically isolated holding brake. The brake cores
must also be safely electrically isolated.
• If the motor power cable is connected to intermediate terminals, the power cables and
brake cables must be laid separately (≥ 300 mm) from each other.
he connecting cables for a 24
V motor holding brake are included in the power cable, then
only the specified cables must be used. These cables must have a separate shield for the
24
V and must be suitable for safe electrical separation.
the motor holding brake conductors must be connected at both ends.
Note
In order that the specified EMC limit values (EN
61800-3) are maintained, only shielded type
MC500 and MC800 power cables must be used. The permissible cable length is 25
m for
ted output currents I
n
from 5 A to 30 A.
The total cable length for the complete drive line
-up is 175 m.