Example of Usage
V560 Series High Performance Closed-Loop Vector Inverter User manual
211
10. EXAMPLE OF USAGE
10.1 ENERGY-SAVING TRANSFORMATION OF ESCALATORS
Operating requirements: Activate operation when it senses people approaching and operate a frequency of
50Hz; If there is no input of sensor signal in 10 seconds, it comes that:
Plan 1) automatically stop;
Plan 2) lower the frequency to 20Hz.
10.1.1 SCHEME DESCRIPTION
Scheme 1:
1. F0.1.16 = 0 (Factory Default) Frequency setting channel
2. F0.2.25 = 2 (Factory Default) Frequency digital setting
3. F0.2.29 = 50.00
Frequency settings
4. F0.3.33= 1
Select the external terminal control of control commands
5. F0.3.35= 0002
Three-line model 1
6. F5.1.06= 1010 Timer 1's clock cycle: 1ms ; Stop- operate trigger-start; state reset of
multifunctional terminal; Multi-cycle timing.
7. F5.1.09= 10000
Timer 1: Cycle reaches 10000ms.
8. F5.1.16= 0003 Timer 1 outputting signal 1: Cycle reaches 0.5s pulse.
9. F3.0.00= 7
Multifunctional terminal D11 is defined as FWD operating terminal
(to receive sensor signals)
10. FF.0.01= 55
Virtual output of SDO1 signal - state of Dl1
11. FF.0.09= 55
Virtual input of SDl1 signal - timer 1 resets terminals
12. FF.0.02= 44
Virtual output of SDO2 signal - timer 1’s cycle reaches 0.5s pulse.
13. FF.0.10= 19
Virtual input of SDl2 signal - three-line operates controlling terminal
14. FF.017= 0010
Phase-reversing connection between SD02 and SDl2
Scheme 2:
1. F0.1.16= 2 Multifunctional terminal selection of frequency settings
2. F0.2.25= 2 Digital setting of frequency channel 1
3. F0.2.26= 2 Digital setting of frequency channel 2
4. F0.2.29= 50 Frequency setting of frequency channel 1
5. F0.2.32= 20 Frequency setting of frequency channel 2
6. F0.3.33= 1 External terminal controlling
7. F0.3.35= 0002
. Three-line model 1
8. F3.0.00= 7
Multifunctional terminal D11 is defined as FWD operating terminal
(to receive sensor signals)
9. F5.1.06= 0000
Timer 1's clock cycle: 1ms ; Operate trigger-start of multifunction
terminals; State reset of multifunctional terminal; Single-cycle timing.