Functional Parameter Table
V560 Series High Performance Closed-Loop Vector Inverter User Manual
71
6.2.33 PROCESS PID SLEEP FUNCTION
(Effective when PID output is used as the frequency command)
Function
Code
Name Setting Range and Description
Minimum
Unit
Factor
y
Default
Change
Limit
F7.2.34 Sleep function
0: Closed 1: Enabled
2: Enabled when the multifunctional input
selection is effective (Function No. 33)
1 0
F7.2.35 Sleep frequency 0.0~[F0.1.21] 0.01 0.0
F7.2.36 Sleep delay 0.1~3600.0Sec. 0.1 60.0
F7.2.37
Awakening deviation
(compared with the
set value )
0.0~100.0(%) 0.1 25.0
F7.2.38 Awakening delay 0.1~3600.0Sec. 0.1 60.0
6.2.34 REVOLUTION SETTING AND FEEDBACK
Function
Code
Name Setting Range and Description
Minimum
Unit
Factory
Default
Change
Limit
F8.0.00
Revolution setting
channel (only applicable
to VC and SVC mode)
0: Set by frequency setting parameter
(F0.1.16)
1: Digital setting (F8.0.03) (maintained
after stop and saved after power-off)
2: Keypad potentiometer
3: Analog inputAI1
4: Analog inputAI2
5: Analog inputAI3 (dual polarity)
6: Frequency input (Fin)
7: MODBUS Fieldbus set value 1
8: MODBUS Fieldbus set value 2
9: Virtual analog input SAI1
10: Virtual mode input SAI2
1 0
F8.0.01
Minimum set signal
corresponding revolution
0~60*[F0.1.21] /
pairs of motor poles (rpm)
1 0
F8.0.02
Maximum set signal
corresponding revolution
0~60*[F0.1.21] /
pairs of motor poles (rpm)
1 1500
F8.0.03 Revolution Digital setting
0~60*[F0.1.21] /
pairs of motor poles (rpm)
1 0
F8.0.04
Revolution feedback
channel
0: Decoder (PG card needs to be
equipped)
1: Single pulse input (Fin port)
2: Analog input AI1
3: Analog input AI2
4: Analog input AI3 (dual polarity)
1 0 ×
F8.0.05
Pulse of decoder per
revolution (PG)
1~8192 1 1024 ×
F8.0.06
PG rotation direction
(Effective for PG card)
0: Phase A leads
1: Phase B leads
1 0 ×