Functional Parameter Table
V560 Series High Performance Closed-Loop Vector Inverter User Manual
52
6.2.10 STEADY RUNNING
Function
Code
Name Setting Range and Description
Minimum
Unit
Factory
Default
Change
Limit
F1.4.39
Acceleration/deceleration current
limiting level
120~180(%) 1 160
F1.4.40 Strong start current limiting level 120~200(%) 1 160
F1.4.41 Strong start current holding time 0.0~5.00Sec. 0.01 0.0
F1.4.42 Function selection for adjustors
_ _ _ X: Overvoltage
suppression adjustor
0: Closed
1: Effective (Frequency
increasing suppression)
2:Terminal inputs
_ _ X _: Under voltage
suppression adjustor
0: Closed 1: Effective
_ X _ _: Frequency modulation
and current limiting adjustor
0: Closed 1: Effective
X _ _ _ : Failure Auto Recovery
Mode
0:Speed tracking start
1:Normal Start
1 0111
F1.4.43
Action level of the overvoltage
adjustor
660~800V 1 740
F1.4.44 Overvoltage adjusting gain 0.10~10.00 0.01 1.00
F1.4.45
Action level of the under voltage
adjustor
[FF.2.35]~480V 1 400V
F1.4.46 Under voltage adjusting gain 0.10~10.00 0.01 1.00
F1.4.47
Action level of the frequency
decreasing and current limiting
adjustor
20~200(%) 1 190
F1.4.48
Adjusting gain of the frequency
decreasing and current limiting
adjustor
0.10~10.00 0.01 1.00
F1.4.49
Recovery times of fault self
resetting
0~5 (the self-recovery function is
deactivated when it is set to 0)
1 0
F1.4.50
The recovery waiting time of fault
self resetting
0.2~100.0Sec. 0.1 1.0
F1.4.51
Time period for self resetting
timing
900~36000Sec. 1 3600