Network Communications
5
5.3 MEMOBUS/Modbus Communications
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 319
Register No.
(Hex.)
Description
002D
U1-11 [Output Terminal Status]
bit 0
MFDO (terminal M1-M2)
1: ON, 0: OFF
bit 1
MFDO (terminal M3-M4)
1: ON, 0: OFF
bit 2
MFDO (terminal M5-M6)
1: ON, 0: OFF
bit 3 - 6 Reserved
bit 7
Fault relay output (terminal MA-MC / MB-MC)
1: ON, 0: OFF
bit 8 - F Reserved
002E - 0030 Reserved
0031 U1-07 [DC Bus Voltage] (unit: 1 V)
0032 U1-09 [Torque Reference] (unit: 1%)
0033 Reserved
0034
0035 Product code 2 [ASCII], region
0036 - 003C Reserved
003D
Communications error description
Note:
The description of the communications error is saved until the fault is reset.
bit 0
CRC Error
bit 1 Data Length Error
bit 2 Reserved
bit 3 Parity Error
bit 4 Overrun Error
bit 5 Framing Error
bit 6 Timeout
bit 7 - F Reserved
003E
Output frequency
Units: min
-1
or r/min
Note:
Set E2-04, E4-04 [Motor Poles].
003F
0.01% units
0040 - 004A Used with U1-xx [Operation Status Monitors]. Refer to the U Monitors for parameter details.