10.9 F: Options
492 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F6-11
(03B7)
CC-Link
Communication Speed
Sets the communication speed for CC-Link communication. Restart the drive after you
change the parameter setting.
0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
0
(0 - 4)
670
F6-14
(03BB)
BUS Error Auto Reset
Sets the automatic reset function for bUS [Option Communication Errors].
0 : Disable
1 : Enabled
0
(0, 1)
670
F6-16
(0B8A)
Gateway Mode
Sets the gateway mode operation and the number of connected slave drives.
0 : Disabled
1 : Enabled: 1 Slave Drives
2 : Enabled: 2 Slave Drives
3 : Enabled: 3 Slave Drives
4 : Enabled: 4 Slave Drives
0
(0 - 4)
671
F6-20
(036B)
MECHATROLINK
Station Address
Sets the station address for MECHATROLINK communication. Restart the drive after
you change this parameter setting.
Note:
The setting range changes if you use MECHATROLINK-II or
MECHATROLINK-III:
MECHATROLINK-II (SI-T3): 20 - 3F
MECHATROLINK-III (SI-ET3): 03 - EF
Set a node address that is different than all other node addresses. Incorrect
parameter settings will cause AEr [Station Address Setting Error] errors and the L.
ERR LED on the option will come on.
The drive detects AEr errors when the station address is 20 or 3F.
0021h
(MECHATROLINK-II:
0020h - 003Fh,
MECHATROLINK-III:
0003h - 00EFh)
673
F6-21
(036C)
MECHATROLINK
Frame Size
Sets the frame size for MECHATROLINK communication. Restart the drive after you
change the parameter setting.
0 : 32byte (M-2) / 64byte (M-3)
1 : 17byte (M-2) / 32byte (M-3)
0
(0, 1)
674
F6-22
(036D)
MECHATROLINK Link
Speed
Sets the communications speed for MECHATROLINK-II. Restart the drive after you
change the parameter setting.
Note:
This parameter is only available with the MECHATROLINK-II option.
0 : 10 Mbps
1 : 4 Mbps
0
(0, 1)
674
F6-23
(036E)
MECHATROLINK
Monitor Select (E)
Sets the MEMOBUS register used for the monitor functions of INV_CTL (drive
operation control command) and INV_I/O (drive I/O control command). Restart the
drive after you change the parameter setting.
0000h
(0000h - FFFFh)
674
F6-24
(036F)
MECHATROLINK
Monitor Select (F)
Sets the MEMOBUS register used for the monitor functions of INV_CTL (drive
operation control command) and INV_I/O (drive I/O control command). Restart the
drive after you change the parameter setting.
0000h
(0000h - FFFFh)
674
F6-25
(03C9)
MECHATROLINK
Watchdog Error Sel
Selects the motor operation when the drive detects E5 [MECHATROLINK Watchdog
Timer Err].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
1
(0 - 3)
674
F6-26
(03CA)
MECHATROLINK
Allowable No of Err
Sets the number of times that the option must detect a bUS alarm to cause a bUS
[Option Communication Error].
2
(2 - 10 times)
675
F6-30
(03CB)
PROFIBUS-DP Node
Address
Sets the node address for PROFIBUS-DP communication. Restart the drive after you
change the parameter setting.
Note:
Be sure to set an address that is different than all other node addresses. Do not set
this parameter to 0.
0
(0 - 125)
675
F6-31
(03CC)
PROFIBUS-DP Clear
Mode Selection
Sets what the drive will do after it receives the Clear Mode command.
0 : Reset
1 : Hold Previous State
0
(0, 1)
675
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV