Parameter List
10
10.10 H: Terminal Functions
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 505
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H2-64
(1B4A)
Expert
Terminal P1 Logical
Operation
Selects the logical operation for the two functions selected by H2-02 [Term M3-M4
Function Selection] and H2-63 [Term M3-M4 Secondary Function].
0
(0 - 8)
710
H2-65
(1B4B)
Expert
Terminal M3-M4 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal
M3-M4.
0.1 s
(0.0 - 25.0 s)
710
H2-66
(1B4C)
Expert
Term M5-M6 Secondary
Function
Sets the second function for terminal M5-M6. Outputs the logical calculation results of
the terminals assigned to functions by H2-03 [Term P1-C1 Function Selection].
F
(0 - FF)
710
H2-67
(1B4D)
Expert
Terminal M5-M6
Logical Operation
Sets the logical operation for the two functions selected by H2-03 [Terminal M5-M6
Function Select] and H2-66 [Term M5-M6 Secondary Function].
0
(0 - 8)
710
H2-68
(1B4E)
Expert
Terminal P2 Minimum
ON Time
Sets the minimum on time used to output the logical calculation results from terminal
M5-M6.
0.1 s
(0.0 - 25.0 s)
710
H2-69
(1B4F)
Expert
Digital Output4
Secondary Func
Sets the second function for terminal P1-C1. Outputs the logical calculation results of
the terminals assigned to functions by H2-04 [Terminal P2-C2 Function Select].
F
(0 - FF)
711
H2-70
(11F9)
Expert
DigitalOutput4 Logical
Operation
Sets the logical operation for the functions set in H2-04 [Terminal P1-C1 Function
Select] and H2-69 [Digital Output4 Secondary Func].
0
(0 - 8)
711
H2-71
(11FA)
Expert
Digital Output 4 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal
P1-C1.
0.1 s
(0.0 - 25.0 s)
711
H2-72
(11FB)
Expert
Digital Output 5
Secondary Func
Sets the second function for terminal P2-C2. The logical calculation results of the
terminals assigned to functions by H2-05 [Term P2-C2 Function Selection] is output.
F
(0 - FF)
711
H2-73
(11FC)
Expert
DigitalOutput5 Logical
Operation
Sets the logical operation for the functions set in H2-05 [Term P2-C2 Function
Selection] and H2-72 [Digital Output 5 Secondary Func].
0
(0 - 8)
711
H2-74
(11FD)
Expert
Digital Output 5 Delay
Time
Sets the minimum ON time used to output the logical calculation results from terminal
P2-C2.
0.1 s
(0.0 - 25.0 s)
711
H2-xx: MFDO Setting Values
Setting Value Function Description Ref.
0 During Run
The terminal activates when you input a Run command and when the drive is outputting voltage.
ON : Drive is running
OFF : Drive is stopping
711
1 Zero Speed
The terminal activates when the output frequency is less than E1-09 [Minimum Output Frequency] or b2-01 [DC
Injection/Zero SpeedThreshold].
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting Description Parameter Used as the Reference
0 Open Loop V/f Control E1-09
1 V/f Control with Encoder E1-09
2 Open Loop Vector b2-01
3 Closed Loop Vector E1-09
4 Advanced OpenLoop Vector Control E1-09
ON : The output frequency is less than the value of E1-09 or b2-01.
OFF : The output frequency is the value of E1-09 or more, or b2-01 or more.
712
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV