10.19 Parameters Changed by E1-03 [V/f Pattern Selection]
556 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
No.
Unit
Setting Value
Control
Method (A1-
02 Setting)
E1-03 0 1 2 3 4 5 6 7 8 9 A B C D E F
OLV
(2)
CLV
(3)
E1-13
*2
V 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
*1
0.0 0.0
E1-14
*2
V 14.0 14.0 14.0 14.0 35.0 50.0 35.0 50.0 18.0 23.0 18.0 23.0 14.0 14.0 14.0
14.0
*1
13.2 -
E1-15
*2
V 7.0 7.0 7.0 7.0 6.0 7.0 6.0 7.0 9.0 11.0 9.0 13.0 7.0 7.0 7.0 7.0
*1
2.4 -
E1-16
*2
V 14.0 14.0 14.0 14.0 35.0 50.0 35.0 50.0 18.0 23.0 18.0 23.0 14.0 14.0 14.0
14.0
*1
13.2 -
E1-17
*2
V 7.0 7.0 7.0 7.0 6.0 7.0 6.0 7.0 9.0 11.0 9.0 13.0 7.0 7.0 7.0 7.0
*1
2.4 -
E1-18
*2
V 14.0 14.0 14.0 14.0 35.0 50.0 35.0 50.0 18.0 23.0 18.0 23.0 14.0 14.0 14.0
14.0
*1
13.2 -
E1-19
*2
V 7.0 7.0 7.0 7.0 6.0 7.0 6.0 7.0 9.0 11.0 9.0 13.0 7.0 7.0 7.0 7.0
*1
2.4 -
*1 Default settings for E1-04 to E1-10, E3-04 to E3-10 [V/f Pattern for Motor 2], and E7-04 to E7-10 [V/f Pattern for Motor 3]. These
settings are the same as those for the V/f pattern when E1-03 = 0 [Const Trq, 50Hz base, 50Hz max].
*2 This is the value for 200 V class drives. Double the value for 400 V class drives.
Table 10.3 Parameters Changed by E1-03 (2215 to 2415 and 4112 to 4605)
No.
Unit
Setting Value
Control
Method (A1-
02 Setting)
E1-03 0 1 2 3 4 5 6 7 8 9 A B C D E F
OLV
(2)
CLV
(3)
E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0
50.0
*1
50.0 50.0
E1-05
*2
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
200.0
*1
200.0 200.0
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0
50.0
*1
50.0 50.0
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 2.5
*1
3.0 -
E1-08
*2
V 12.0 12.0 12.0 12.0 35.0 50.0 35.0 50.0 15.0 20.0 15.0 20.0 12.0 12.0 12.0
12.0
*1
13.2 -
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.3
*1
0.5 0.0
E1-10
*2
V 6.0 6.0 6.0 6.0 5.0 6.0 5.0 6.0 7.0 9.0 7.0 11.0 6.0 6.0 6.0 6.0
*1
2.4 -
E1-11 Hz 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
*1
0.0 0.0
E1-12
*2
V 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
*1
0.0 0.0
E1-13
*2
V 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
*1
0.0 0.0
E1-14
*2
V 12.0 12.0 12.0 12.0 35.0 50.0 35.0 50.0 15.0 20.0 15.0 20.0 12.0 12.0 12.0
12.0
*1
13.2 -
E1-15
*2
V 6.0 6.0 6.0 6.0 5.0 6.0 5.0 6.0 7.0 9.0 7.0 11.0 6.0 6.0 6.0 6.0
*1
2.4 -
E1-16
*2
V 12.0 12.0 12.0 12.0 35.0 50.0 35.0 50.0 15.0 20.0 15.0 20.0 12.0 12.0 12.0
12.0
*1
13.2 -
E1-17
*2
V 6.0 6.0 6.0 6.0 5.0 6.0 5.0 6.0 7.0 9.0 7.0 11.0 6.0 6.0 6.0 6.0
*1
2.4 -
E1-18
*2
V 12.0 12.0 12.0 12.0 35.0 50.0 35.0 50.0 15.0 20.0 15.0 20.0 12.0 12.0 12.0
12.0
*1
13.2 -
E1-19
*2
V 6.0 6.0 6.0 6.0 5.0 6.0 5.0 6.0 7.0 9.0 7.0 11.0 6.0 6.0 6.0 6.0
*1
2.4 -
*1 Default settings for E1-04 to E1-10, E3-04 to E3-10 [V/f Pattern for Motor 2], and E7-04 to E7-10 [V/f Pattern for Motor 3]. These
settings are the same as those for the V/f pattern when E1-03 = 0 [Const Trq, 50Hz base, 50Hz max].
*2 This is the value for 200 V class drives. Double the value for 400 V class drives.