Parameter Details
11
11.4 C: Tuning
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 621
Table 11.15 Wiring Distance
Wiring Distance Up to 50 m Up to 100 m Greater than 100 m
C6-02 [Carrier Frequency Selection] 1 to F (up to 15 kHz) 1 to 2 (up to 5 kHz), 7 1 (up to 2 kHz), 7
C6-03: Carrier Frequency Upper Limit
No.
(Hex.)
Name Description
Default
(Range)
C6-03
(0225)
Carrier Frequency Upper
Limit
Sets the upper limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
Setting a Fixed User-Defined Carrier Frequency
When you cannot use C6-02 to set a carrier frequency between set selectable values, you can set the value in C6-
03. The carrier frequency will be fixed to the value set to C6-03.
When A1-02 = 0, 1 [Control Method Selection = V/f, CL-V/f], set C6-03 = C6-04 [Carrier Frequency Lower
Limit] to fix the carrier frequency.
Setting a Variable Carrier Frequency to Agree with the Output Frequency
When A1-02 = 0, 1, set C6-03, C6-04, and C6-05 [Carrier Freq Proportional Gain] as shown in
Figure 11.40 to
make the carrier frequency change linearly with the output frequency.
Figure 11.40 Setting a Variable Carrier Frequency to Agree with the Output Frequency
Note:
When C6-05 7, the drive disables C6-04. The carrier frequency is fixed to the value set to C6-03.
The drive detects oPE11 [Carrier Frequency Setting Error] when these conditions are correct at the same time:
C6-05 6
C6-04 C6-03
C6-04: Carrier Frequency Lower Limit
No.
(Hex.)
Name Description
Default
(Range)
C6-04
(0226)
Carrier Frequency Lower
Limit
Sets the lower limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
Set C6-03 [Carrier Frequency Upper Limit], C6-04, and C6-05 [Carrier Freq Proportional Gain] to make the
carrier frequency change linearly with the output frequency.
Note:
The drive detects oPE11 [Carrier Frequency Setting Error] when these conditions are correct at the same time:
C6-04 C6-03
C6-05 6
C6-05: Carrier Freq Proportional Gain
No.
(Hex.)
Name Description
Default
(Range)
C6-05
(0227)
Carrier Freq Proportional
Gain
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier Frequency Selection
= User Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(0 - 99)
Set C6-03 [Carrier Frequency Upper Limit], C6-04 [Carrier Frequency Lower Limit], and C6-05 to make the
carrier frequency change linearly with the output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV