Parameter Details
11
11.6 E: Motor Parameters
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 637
2003 - 2018, 4002 - 4009 2025 - 2180, 4015 - 4091 2215 - 2415, 4112 - 4605
8 : High Trq, 50Hz, 25% Vmin boost
This pattern is used when moderate torque is required during startup.
Select this pattern only in the following circumstances.
Wiring distance between the drive and motor is at least 150 m.
An AC reactor is connected to the drive output.
Note:
The voltage values in the figure represent those when using 200 V class drives. Double the values for 400 V class drives.
2003 - 2018, 4002 - 4009 2025 - 2180, 4015 - 4091 2215 - 2415, 4112 - 4605
9 : High Trq, 50Hz, 65% Vmin boost
This pattern is used when strong torque is required during startup.
Select this pattern only in the following circumstances.
Wiring distance between the drive and motor is at least 150 m.
An AC reactor is connected to the drive output.
Note:
The voltage values in the figure represent those when using 200 V class drives. Double the values for 400 V class drives.
2003 - 2018, 4002 - 4009 2025 - 2180, 4015 - 4091 2215 - 2415, 4112 - 4605
A : High Trq, 60Hz, 25% Vmin boost
This pattern is used when moderate torque is required during startup.
Select this pattern only in the following circumstances.
Wiring distance between the drive and motor is at least 150 m.
An AC reactor is connected to the drive output.
Note:
The voltage values in the figure represent those when using 200 V class drives. Double the values for 400 V class drives.