EasyManuals Logo

YASKAWA CR700 Technical Manual

YASKAWA CR700
886 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #655 background imageLoading...
Page #655 background image
Parameter Details
11
11.7 F: Options
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 655
F1-20: Encoder 1 PCB Disconnect Detect
No.
(Hex.)
Name Description
Default
(Range)
F1-20
(03B4)
Encoder 1 PCB Disconnect
Detect
Sets the function that enables and disables detection of a disconnected PG-X3 encoder connection
cable. Detects PGoH [Encoder (PG) Hardware Fault] when F1-20 = 1.
1
(0, 1)
0 : Disabled
1 : Enabled
F1-21: Encoder 1 Signal Selection
No.
(Hex.)
Name Description
Default
(Range)
F1-21
(03BC)
Encoder 1 Signal Selection
Sets the number of channels for the signal to the encoder option.
0
(0, 1)
0 : A Pulse Detection
1 : AB Pulse Detection
F1-30: Motor 2 Encoder PCB Port Select
No.
(Hex.)
Name Description
Default
(Range)
F1-30
(03AA)
Motor 2 Encoder PCB Port
Select
Sets the connector used when the motor 2 encoder option is installed in the drive.
1
(0, 1)
0 : CN5-C
Set when the speed feedback from the encoder for motor 1 and motor 2 is received by one option card while such
signals are switched externally.
1 : CN5-B
Set when the speed feedback from the encoder for motor 1 and motor 2 is received by two PG option cards
independently.
F1-31: Encoder 2 Pulse Count (PPR)
No.
(Hex.)
Name Description
Default
(Range)
F1-31
(03B0)
Encoder 2 Pulse Count
(PPR)
Sets the number of output pulses per revolution of the encoder. This parameter is for motor 2.
1024
(1 - 60000 ppr)
F1-32: PG 2 Rotation Selection
No.
(Hex.)
Name Description
Default
(Range)
F1-32
(03B1)
Encoder 2 Rotation
Selection
Sets the output sequence for the A and B pulses from the encoder, assuming that the motor is
operating in the forward direction. This parameter is for motor 2.
0
(0, 1)
Refer to the installation manual included with the option card for more information on how to confirm and set the
encoder pulse output sequence.
0 : Pulse A leads in FWD Direction
1 : Pulse B leads in FWD Direction
F1-33: Encoder 2 Gear Teeth 1
No.
(Hex.)
Name Description
Default
(Range)
F1-33
(03B2)
Encoder 2 Gear Teeth 1
Sets the number of gear teeth on the motor side for motor 2. This parameter and F1-34 [Encoder
2 Gear Teeth 2] set the gear ratio between the motor and encoder.
0
(0 - 1000)
After you set the number of gear teeth, the drive uses this formula to calculate the motor speed:
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV

Table of Contents

Other manuals for YASKAWA CR700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CR700 and is the answer not in the manual?

YASKAWA CR700 Specifications

General IconGeneral
BrandYASKAWA
ModelCR700
CategoryDC Drives
LanguageEnglish

Related product manuals