11.8 H: Terminal Functions
720 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
2F: Maintenance Notification
Setting Value Function Description
2F Maintenance Notification
The terminal activates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
IGBT
Cooling fan
Capacitor
Soft charge bypass relay
Note:
Refer to Alarm Outputs for Maintenance Monitors for more information.
30: During Torque Limit
Setting Value Function Description
30 During Torque Limit
The terminal activates when the torque reference is the torque limit set with L7 parameters, H3-02, H3-06, or H3-10 [MFAI
Function Selection].
Note:
Refer to L7: Torque Limit for more information.
33: Zero Servo Complete
Setting Value Function Description
33 Zero Servo Complete
The terminal activates when positioning in the range set with b9-02 [Zero Servo Completion Window] completes after sending
the Zero-Servo command.
Note:
Refer to b9: Zero Servo for more information.
37: During Frequency Output
Setting Value Function Description
37 During Frequency Output
The terminal activates when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
Note:
The terminal turns off in any of these conditions:
During Stop
During baseblock
During DC Injection Braking (initial excitation)
Figure 11.68 Active Frequency Output Time Chart
39: Watt Hour Pulse Output
Setting Value Function Description
39 Watt Hour Pulse Output
Outputs the pulse that shows the watt hours.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV