11.8 H: Terminal Functions
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 719
■ 1C: Motor 2 Selected
Setting Value Function Description
1C Motor 2 Selected
The terminal activates when you select motor 2.
ON : Motor 2 Selection
OFF : Motor 1 Selected
■ 1D: During Regeneration
Setting Value Function Description
1D During Regeneration
The terminal activates on when the motor is regenerating.
ON : Motor is regenerating.
OFF : Motor is operating or stopped.
■ 1F: Motor Overload Alarm (oL1)
Setting Value Function Description
1F Motor Overload Alarm
(oL1)
The terminal activates when the electronic thermal protection value of the motor overload protective function is a minimum of
90% of the detection level.
Note:
Refer to “L1-01: Motor Overload (oL1) Protection” for more information.
■ 20: Drive Overheat Pre-Alarm (oH)
Setting Value Function Description
20 Drive Overheat Pre-Alarm
(oH)
The terminal activates when the drive heatsink temperature is at the level set with L8-02 [Overheat Alarm Level].
Note:
Refer to “L8-02: Overheat Alarm Level” for more information.
■ 21: Brake Release Command
Setting Value Function Description
21 Brake Release Command
Set the sequence external to the drive to release the brake when the terminal turns ON and holds the brake when the terminal
turns OFF.
ON : The brake is released.
OFF : The brake is tightened.
Note:
Refer to
Brake Sequence on page 195 for details.
■ 22: Overload Detection (N.O.)
Setting Value Function Description
22 Overload Detection (N.O.)
The terminal activates when the drive detects an overload.
Note:
Refer to
Overload Detection on page 213 for details.
■ 23: Weight Det N.C.
Setting Value Function Description
23 Weight Det N.C.
The terminal deactivates when the drive detects an overload.
Note:
Refer to
Overload Detection on page 213 for details.