Parameter Details
11
11.11 o: Keypad-Related Settings
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 797
No. Item Number of
characters
Description
24 to 27 Reserved 4 -
28 Row number 6 Row number (Hex.) in the data log file
*1 The text string of [0000] is generated when there is no data log monitor selected.
*2 Refer to the following table for information on unit codes.
Unit code (Hex.) Unit Unit code (Hex.) Unit Unit code (Hex.) Unit Unit code (Hex.) Unit
00 – 08 PPR 10 H 18 0H
01 Hz 09 kW 11 V 19 –
02 RPM 0A Ω 12 us 1A –
03 % 0B ms 13 min 1B –
04 VAC 0C kHz 14 °C 1C –
05 VDC 0D PSI 15 W 1D –
06 A 0E MPM 16 kWH 1E –
07 sec 0F FPM 17 MWH 1F –
Third and Subsequent Rows: Log Data
The following example illustrates the data text strings and data generated for the third row of log data.
Example of generated data:
02,0012,160107111239,1770,1770,00BE,0118,0028,0000,0000,0000,0000,0000,0000,0000,00000C
No. Item Number of
characters
Description
1 Attribute 2 [02] represents that the record is a monitor data record.
2 File number 4 The [xxx] part of the [GLOG0xxx.csv] filename is a 3-digit decimal number generated in hexadecimal format.
3 Time stamp 12 Data log data was retrieved (YYMMDDHHMMSS)
4 Log Monitor Data 1 4 Log monitor data (Hex.) of the monitor selected with o5-03 [Log Monitor Data 1]
5 Log Monitor Data 2 4 Log monitor data (Hex.) of the monitor selected with o5-04 [Log Monitor Data 2]
: : : :
13 Log Monitor Data 10 4 Log monitor data (Hex.) of the monitor selected with o5-12 [Log Monitor Data 10]
14 Reserved 4 -
15 Encoding data 4 Encoding data for log monitor data 1 through 10 (Hex.)
Bits 0 through 9 represent the encoding of log monitor data 1 1 through 10. A bit value of 1 represents that the data
represents a negative value. (Log monitor data 1 through 10 is absolute value data without encoding)
Example when log monitor data 2, 5, and 8 represent negative values: Bits 1, 4, and 7 have values of 1, and so the
encoding data = 0010010010 (Bin.) = 0092 (Hex.)
16 Row number 6 Row number (Hex.) in the data log file
■ o5-01: Log Start/Stop Selection
No.
(Hex.)
Name Description
Default
(Range)
o5-01
(1551)
RUN
Log Start/Stop Selection
Sets the data log function. This parameter is only available when using an LCD keypad.
0
(0 - 1)
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].
■ o5-02: Log Sampling Interval
No.
(Hex.)
Name Description
Default
(Range)
o5-02
(1552)
RUN
Log Sampling Interval
Sets the data log sampling cycle. This parameter is only available on an LCD keypad.
1000 ms
(100 - 60000 ms)