11.11 o: Keypad-Related Settings
798 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
o5-03: Log Monitor Data 1
No.
(Hex.)
Name Description
Default
(Range)
o5-03
(1553)
RUN
Log Monitor Data 1
Sets the data log monitor. This parameter is only available when using an LCD keypad.
101
(000, 101 - 999)
Note:
Set the number of the U monitor to record the data log.
For example, to show U1-01 [Frequency Reference], set o5-03 = 101. When it is not necessary to set data log monitors, set this
parameter to 000. You cannot set U2 monitor [Fault Trace] or U3 Monitor [Fault History].
o5-04: Log Monitor Data 2
No.
(Hex.)
Name Description
Default
(Range)
o5-04
(1554)
RUN
Log Monitor Data 2
Sets the data log monitor. This parameter is only available when using an LCD keypad.
102
(000, 101 - 999)
Note:
Set the U monitor number you will log.
For example, to show U1-02 [Output Frequency], set o5-04 = 102. When it is not necessary to set data log monitor, set this parameter to
000.
o5-05: Log Monitor Data 3
No.
(Hex.)
Name Description
Default
(Range)
o5-05
(1555)
RUN
Log Monitor Data 3
Sets the data log monitor. This parameter is only available when using an LCD keypad.
103
(000, 101 - 999)
Note:
Sets the number of the U monitor you will log.
For example, to show U1-03 [Output Current], set o5-05 = 103. When it is not necessary to set data log monitors, set this parameter to
000. You cannot select U2 monitor [Fault Trace] or U3 Monitor [Fault History].
o5-06: Log Monitor Data 4
No.
(Hex.)
Name Description
Default
(Range)
o5-06
(1556)
RUN
Log Monitor Data 4
Sets the data log monitor. This parameter is only available when using an LCD keypad.
107
(000, 101 - 999)
Note:
Sets the number of the U monitor you will log.
For example, to show U1-07 [DC Bus Voltage], set o5-06 = 107. When it is not necessary to set data log monitors, set this parameter to
000. You cannot select U2 monitor [Fault Trace] or U3 Monitor [Fault History].
o5-07: Log Monitor Data 5
No.
(Hex.)
Name Description
Default
(Range)
o5-07
(1557)
RUN
Log Monitor Data 5
Sets the data log monitor. This parameter is only available when using an LCD keypad.
108
(000, 101 - 999)
Note:
Sets the number of the U monitor you will log.
For example, to show U1-08 [Output Power], set o5-07 = 108. When it is not necessary to set data log monitors, set this parameter to
000. You cannot select U2 monitor [Fault Trace] or U3 Monitor [Fault History].