SA-54 Pos PI Limit
No.
(Hex.)
Name Description
Default Setting
(Range)
SA-54
(1ACE)
RUN
Pos PI Limit
Sets the limit (+/-) on position controller output at maximum
output frequency (E1-04) %.
Note: Enabled only when set to Position Synchronization
mode.
8.00%
(0.00 - 10.00%)
SA-55 Pos Trim Mode
No.
(Hex.)
Name Description
Default Setting
(Range)
SA-55
(1ACF)
RUN
Pos Trim Mode
Selects how to adjust output of the position controller.
0
(0, 1)
0: Constant
Position controller output does not depend on the speed level of the master.
1: Speed Prop
Position controller output is directly proportional to the speed level of the master.
Example: When EA-04 is set to 60 Hz, SA-56 is set to 10%, and position controller output is
10%:
• SA-55 = 0
The PI output amount added to the frequency reference is 60 Hz × 10% = 6 Hz, regardless of
the speed level of the master.
• SA-55 = 1
① When the slave frequency reference (30 Hz) is larger than 6 Hz (E1-04 (60 Hz) × SA-56
(10%)):
② When the slave frequency reference is smaller than 6 Hz (E1-04 (60 Hz) × SA-56
(10%)):
Position controller output after adjustment =
E1-04 × Position controller output (10%) × SA-56 (10%) = 0.6 Hz
Position controller output is limited by SA-56.
SA-56 SpdProp LowerLim
No.
(Hex.)
Name Description
Default Setting
(Range)
SA-56
(1AD0)
RUN
SpdProp LowerLim
Sets the lower limit value of the speed controller adjustment
when SA-55 is set to 1.
10.00%
(0.00 - 100.00%)
Position controller output after adjustment
=
60 Hz × 10% ×
30 Hz
60 Hz
= 3 Hz
E1-04
Frequency
E1-04 × Position controller output (10%) ×
=