6-43
IM 05P02C41-01EN
Monitoring and Control of Regular Operations
6
Executing Advance advances the program to the next segment, irrespective of the
junctioncode(JC).
Advance is performed as follows depending on the segment to execute and the operating
state.
When executing Advance in the last segment:
The program switches to Reset operation (when JC=CONT), Local operation, or
Remoteoperationdependingonthejunctioncode(JC).
When executing Advance in the repeat cycle end segment:
The program performs a repeat operation.
When executing Advance during the hold operation:
The program releases the hold state and restarts program pattern operation from the
next segment.
Executing Advance shortens the segment time of the segment for which operation is in
progress and the time of the event.