EasyManua.ls Logo

YOKOGAWA UP55A - Adjusting Valve Position Manually

YOKOGAWA UP55A
516 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10-29
IM 05P02C41-01EN
Output (Control and Retransmission) Functions
10.16.3 AdjustingValvePositionManually
Description
Thefollowingproceduredescribeshowtoadjustvalvepositionmanually.
(1) Verify that the wirings are correct.
(2) Set the operation mode to MAN.
(3) Reset the valve position (Set V.RS=ON).
(4) Display the fully-closed valve position setting (V.L), determine the fully-closed
position while holding down the Down arrow (
) key, and press the SET/ENTER
key.
(5) Display the fully-opened valve position setting (V.H), determine the fully-opened
position while holding down the Up arrow (
) key, and press the SET/ENTER key.
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
V.RS
Valve position
setting reset
EASY
Setting V.RS to ON resets the
valveadjustmentsettingsand
causes the indication “V.RS” to
blink.
OUT
V.L
Fully-closed valve
position setting
EASY
Pressing the SET/ENTER key
with valve position set to the fully-
closed position by Down arrow
keycausestheadjustedvalueto
bestored.WhenV.Ladjustmentis
complete, V.L stops blinking.
V.H
Fully-opened valve
position setting
EASY
Pressing the SET/ENTER key
with valve position set to the fully-
opened position by Up arrow key
causestheadjustedvaluetobe
stored.WhenV.Hadjustmentis
complete, V.H stops blinking
10
10.16AdjustingMotor-operatedValvePosition(PositionProportionalOutput)