8-72
IM 05P02C41-01EN
8.13
SettingControllerActionatPowerON(RestartMode)
Description
For details, see Chapter 15, “Power Failure Recovery Processing.”
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
R.MD Restart Mode STD
CONT: Continue action set before
power failure. (Continue operation
mode.)
MAN: Start from MAN. (Continue
operation mode.)
RESET: Start from AUTO and RESET.
Outputs the preset output value.
Set how the controller should recover
from a power failure of 5 seconds or
more.
SYS
Operation mode: PROG, RESET, LOCAL, REMOTE
The preset output (PO) is output in MAN or RESET mode.