17-29
IM 05P02C41-01EN
Installation and Wiring
17
17.4.16 PROFIBUS-DPCommunicationInterfaceWiring
(1) Remove the terminal block
Hold both ends of the terminal block and pull straight.
(2) Connect the wires
Flat-blade screwdriver
Recommended length of stripped wire: 7mm
(3) Connect the terminal block
Hold both ends of the terminal block, align with the connector
on the UT side, and push the terminal block into the connector.
Multiple wiring (multi-drop) of connector
Multiple wiring of the UTAdvanced connector with other devices is possible within
the following multi-wire connection capacity range.
Multi-wire connection capacity (Two wires with the same cross-sectional area)
• Single wire 0.2 to 1.0 mm
2
/twisted wire 0.2 to 1.5 mm
2
• Twisted wire with bar terminal (without plastic sleeve) 0.25 to 1.0 mm
2
• Twisted wire with twin bar terminals (with plastic sleeve) 0.5 to 1.5 mm
2
17.4Wiring