6-48
IM 05P02C41-01EN
6.6.9 SwitchingbetweenLocal(LSP)andCascade
SelectingbyMODEKey
SettingDisplay
CAS lamp is lit in
CAS mode.
(The lamp is lit after
operation right.)
Each time you press the key,
Operation modes is switched.
Display MODE CAS (blinking), and press the SET/ENTER key.
SelectingbyOperationModeParameter
SettingDisplay
Parameter Setting Display
Operation Display > PARAMETER key for 3 seconds (to
[MODE] Menu Display) > SET/ENTER key (The setting
parameter is displayed.) > Downarrow key (The setting
parameter is displayed.)
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
L.C
Local (LSP) /
cascade switch
EASY
LSP: Local (LSP
CAS: Cascade
MODE
Description
Local (LSP) and Cascade can be switched when the control mode is set to cascade
control.
When the switching is completed using the above method, the screen is switched to SP
Display.
6.6SwitchingOperationModes