9-47
IM 05P02C41-01EN
Program Pattern Functions
9
9.13.5 DeletingtheProgramPattern
Description
This allows specifying the program pattern number to delete.
This allows deleting all programs in the controller.
Clearingallprogrampatterndata:12.2InitializingParameterSettingstoFactoryDefaultValues
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
CLR.P
Program pattern
clearance
PRO
1 to 30 or 99 (99 when the option
“/AP”isspecied)
EDIT
9.13.6 ListoftheErrorCode
Description
Error Indication at Program Pattern Creation and Editing
Error code Errorinformation Causeoferror
ERR01 Pattern creation or editing
is disable during program
operation.
Deleting or copying of the program pattern, or inserting
or deleting of the segment was excuted during program
operation.
ERR22 Segment write error The total number of segments exceeded 300 or 600
(600whentheoption“/AP”isspecied).
ERR23 Segment insert error New segment cannot be inserted because the number
of segments in a pattern exceeded 99.
ERR32 Patternsourcespecication
error
No pattern exists in the source.
ERR33 Pattern destination
specicationerror
Patterns already exist in the destination.
ERR41 Pattern delete errror The pattern to be deleted does not exist.
Error Codes in Communication
Error code Errorinformation Causeoferror
0 No error Normal end.
1 Pattern creation or editing
is disable during program
operation.
Deleting or copying of the program pattern, or inserting
or deleting of the segment was excuted during program
operation.
2 Pattern number error Thespeciedpatternnumberdoesnotexist.
1to30or99(99whentheoption“/AP”isspecied)
3 Segment number error Thespeciedsegmentnumberdoesnotexist.
1 to 99
22 Segment write error The total number of segments exceeded 300 or 600
(600whentheoption“/AP”isspecied).
31 Pattern copy error No pattern exists in the source, or patterns already
exist in the destination.
41 Pattern delete errror The pattern to be deleted does not exist.
9.13EditingtheProgramPattern

Table of Contents

Other manuals for YOKOGAWA UP55A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UP55A and is the answer not in the manual?

YOKOGAWA UP55A Specifications

General IconGeneral
BrandYOKOGAWA
ModelUP55A
CategoryController
LanguageEnglish

Related product manuals