6-51
IM 05P02C41-01EN
Monitoring and Control of Regular Operations
6
6.8 Fast-forwardingProgramPattern
PerformingbyMODEKey
SettingDisplay
Every time you press the MODE key, the
operation mode is switched.
Display P.FWD (fast-forwarding), and press the
SET/ENTER key.
PerformingbyOperationModeParameter
SettingDisplay
Parameter Setting Display
Operation Display > PARAMETER key for 3 seconds (to
[MODE] Menu Display) > SET/ENTER key (The setting
parameter is displayed.) > Downarrow key (The setting
parameter is displayed.)
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
P.FWD
Fast-forwarding
of program
operation
EASY
1: Normal, 2: Twice, 5: Five
times,10: Ten times
MODE
Description
This function is used to make sure that the program pattern is set correctly. It fast
forwards only the segment time and the time of the time event. When the fast-forwarding
function is executed, when the operation mode is switched to local, remote, or reset
operation, or when power is turned on, P.FWD returns to 1 (normal).
Other functions (alarm delay timer, PV velocity alarm, output velocity limiter, and ladder
program time) work at normal speed.