8-48
IM 05P02C41-01EN
WhentheHeatingSideisinON/OFFControlandtheCoolingSideisinPIDControl:
The following shows the formula and operation example.
HOUT = OUT > ( 50% + + )
Other than this case, maintain current state.
Output turns on when
2
DB
2
HYS
*: OUT: control output, HOUT: heating-side control output,
COUT: cooling-side control output, DB: dead band, and
HYS: heating-side hysteresis
COUT = ( 50%
OUT
) × 2
2
DB
PositiveDeadBand
0%
Dead band
(DB)
Dead
band
(DB)
Hysteresis (HYS)
Cooling-side control output (%) Heating-side control output (%)
0%
50%
Control computation output
100%
100%
Cooling-side
control output
high limit
(OHc)
0%
100%
0% 50% 100%
(OUT)
NegativeDeadBand
0%
0%
50% 100%
100%
0%
100%
0% 50% 100%
Dead band
(DB)
Dead band
(DB)
Hysteresis (HYS)
Cooling-side control output (%)
Heating-side control output (%)
Control computation output
Cooling-side
control output
high limit
(OHc)
(OUT)
8.2SettingControlType(CNT)