9-14
IM 05P02C41-01EN
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
SSP
Starting target
setpoint
EASY
0.0 to 100.0% of PV input range
(EU)
(Setting range: P.RL to P.RH)
PROG
STC Start code EASY
SSP: Program operation begins
with the starting target setpoint.
RAMP:Ramp-prioritizedPVstart
TIME:Time-prioritizedPVstart
LSP: Local-mode start
RSP: Remote-mode start
Note 1: When the program pattern-2 retransmission is selected (PT2.G=ON), the second loop is
also displayed for the parameter SSP. (LP2 lamp is lit.)
9.3SettingtheProgramStartingConditions(STC)