ELECTRICAL DATA 76 77 78
Unit Data DCF066DX-16FVW0 DCF069DX-16FWW0 DCF073TX-16GPPY
Nominal Run Amps (1) A 425.1 437.3 463.3
Maximum Start Amps A 688.5 672.7 726.7
Recommended Mains Fuse Size A 450 500 500
Evaporator
Immersion Heater Rating W 170 170 250
Condenser Fan - Per Fan (EC)
Quantity 16 16 16
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 55.2 / 59.2 59.2 / 59.2 59.2 / 59.2 / 47.9
Quantity 3 + 3 3 + 3 2 + 2 + 3
Motor Rating kW 33.1 / 36.2 36.2 / 36.2 36.2 / 36.2 / 29.8
Sump Heater Rating W 140 140 140
Start Amps (2) A 326 / 298 298 / 298 298 / 298 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 397.7 411.4 438.6
Reactive power reduction/saving (4) kVAr 49.0 46.9 45.6
Maximum Start Amps A 661.1 646.8 702.0
Recommended Mains Fuse Size A 450 500 500
Electronic Soft-start
Nominal Run Amps A 425.1 437.3 463.3
Maximum Start Amps A 558.1 553.5 596.3
Recommended Mains Fuse A 450 500 500
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 397.7 411.4 438.6
Maximum Start Amps A 530.7 527.6 571.6
Recommended Mains Fuse Size A 450 500 500
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 21.2 21.2 21.2
Unit Nominal Run Amps A 446.2 458.3 484.3
Recommended Mains Fuse Size A 500 500 560
Motor Rating kW 12.1 12.1 12.1
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 28.5 28.5 28.5
Unit Nominal Run Amps A 453.5 465.6 491.6
Recommended Mains Fuse Size A 500 500 560
Motor Rating kW 16.4 16.4 16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 19.8 19.8 19.8
Unit Nominal Run Amps A 441.1 453.3 479.5
Recommended Mains Fuse Size A 500 500 500
Motor Rating kW 12.4 12.4 12.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 26.9 26.9 26.9
Unit Nominal Run Amps A 446.8 459.1 485.2
Recommended Mains Fuse Size A 500 500 560
Motor Rating kW 16.8 16.8 16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet