ELECTRICAL DATA 82 83 84
Unit Data DCF082TX-18GYYY DCF085TX-17HYVV DCF089TX-18HVVV
Nominal Run Amps (1) A 523.4 568.0 596.5
Maximum Start Amps A 799.0 835.4 863.9
Recommended Mains Fuse Size A 560 630 630
Evaporator
Immersion Heater Rating W 250 250 250
Condenser Fan - Per Fan (EC)
Quantity 18 17 18
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 47.9 / 47.9 / 47.9 47.9 / 55.2 / 55.2 55.2 / 55.2 / 55.2
Quantity 3 + 3 + 3 3 + 3 + 3 3 + 3 + 3
Motor Rating kW 29.8 / 29.8 / 29.8 29.8 / 33.1 / 33.1 33.1 / 33.1 / 33.1
Sump Heater Rating W 140 140 140
Start Amps (2) A 326 / 326 / 326 326 / 326 / 326 326 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 500.7 531.5 552.7
Reactive power reduction/saving (4) kVAr 42.8 65.2 76.5
Maximum Start Amps A 776.3 798.9 820.1
Recommended Mains Fuse Size A 560 630 630
Electronic Soft-start
Nominal Run Amps A 523.4 568.0 596.5
Maximum Start Amps A 668.6 705.0 733.5
Recommended Mains Fuse A 560 630 630
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 500.7 531.5 552.7
Maximum Start Amps A 645.9 668.5 689.7
Recommended Mains Fuse Size A 560 630 630
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 28.5 28.5 28.5
Unit Nominal Run Amps A 551.5 596.3 624.9
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 16.4 16.4 16.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 35.0 35.0 35.0
Unit Nominal Run Amps A 558.0 602.8 631.4
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 20.3 20.3 20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 26.9 26.9 26.9
Unit Nominal Run Amps A 545.5 589.6 617.9
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 16.8 16.8 16.8
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 33.2 33.2 33.2
Unit Nominal Run Amps A 550.7 594.7 622.9
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 20.7 20.7 20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet