EasyManua.ls Logo

AIREDALE DeltaChill - Page 133

AIREDALE DeltaChill
302 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technic al
Chillers
DeltaChill™ Air Cooled and FreeCool
133
Chiller Technical Manual 7267818 V1.13.0_01_2018
FreeCool
ELECTRICAL DATA 82 83 84
Unit Data DCF082TX-18GYYY DCF085TX-17HYVV DCF089TX-18HVVV
Nominal Run Amps (1) A 523.4 568.0 596.5
Maximum Start Amps A 799.0 835.4 863.9
Recommended Mains Fuse Size A 560 630 630
Evaporator
Immersion Heater Rating W 250 250 250
Condenser Fan - Per Fan (EC)
Quantity 18 17 18
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 47.9 / 47.9 / 47.9 47.9 / 55.2 / 55.2 55.2 / 55.2 / 55.2
Quantity 3 + 3 + 3 3 + 3 + 3 3 + 3 + 3
Motor Rating kW 29.8 / 29.8 / 29.8 29.8 / 33.1 / 33.1 33.1 / 33.1 / 33.1
Sump Heater Rating W 140 140 140
Start Amps (2) A 326 / 326 / 326 326 / 326 / 326 326 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 500.7 531.5 552.7
Reactive power reduction/saving (4) kVAr 42.8 65.2 76.5
Maximum Start Amps A 776.3 798.9 820.1
Recommended Mains Fuse Size A 560 630 630
Electronic Soft-start
Nominal Run Amps A 523.4 568.0 596.5
Maximum Start Amps A 668.6 705.0 733.5
Recommended Mains Fuse A 560 630 630
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 500.7 531.5 552.7
Maximum Start Amps A 645.9 668.5 689.7
Recommended Mains Fuse Size A 560 630 630
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 28.5 28.5 28.5
Unit Nominal Run Amps A 551.5 596.3 624.9
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 16.4 16.4 16.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 35.0 35.0 35.0
Unit Nominal Run Amps A 558.0 602.8 631.4
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 20.3 20.3 20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 26.9 26.9 26.9
Unit Nominal Run Amps A 545.5 589.6 617.9
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 16.8 16.8 16.8
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 33.2 33.2 33.2
Unit Nominal Run Amps A 550.7 594.7 622.9
Recommended Mains Fuse Size A 630 630 670
Motor Rating kW 20.7 20.7 20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet

Table of Contents

Related product manuals