ELECTRICAL DATA 85 86 87
Unit Data DCF092TX-18HVVW DCF094TX-18HVWW DCF096TX-18HWWW
Nominal Run Amps (1) A 608.5 620.6 632.8
Maximum Start Amps A 871.9 884.0 868.2
Recommended Mains Fuse Size A 630 670 670
Evaporator
Immersion Heater Rating W 250 250 250
Condenser Fan - Per Fan (EC)
Quantity 18 18 18
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 55.2 / 55.2 / 59.2 55.2 / 59.2 / 59.2 59.2 / 59.2 / 59.2
Quantity 3 + 3 + 3 3 + 3 + 3 3 + 3 + 3
Motor Rating kW 33.1 / 33.1 / 36.2 33.1 / 36.2 / 36.2 36.2 / 36.2 / 36.2
Sump Heater Rating W 140 140 140
Start Amps (2) A 326 / 326 / 298 326 / 298 / 298 298 / 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 566.4 580.1 593.7
Reactive power reduction/saving (4) kVAr 74.4 72.3 70.3
Maximum Start Amps A 829.8 843.5 829.1
Recommended Mains Fuse Size A 630 670 670
Electronic Soft-start
Nominal Run Amps A 608.5 620.6 632.8
Maximum Start Amps A 741.5 753.6 749.0
Recommended Mains Fuse A 630 670 670
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 566.4 580.1 593.7
Maximum Start Amps A 699.4 713.1 709.9
Recommended Mains Fuse Size A 630 670 670
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 28.5 28.5 28.5
Unit Nominal Run Amps A 636.9 649.0 661.1
Recommended Mains Fuse Size A 670 670 710
Motor Rating kW 16.4 16.4 16.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 35.0 35.0 35.0
Unit Nominal Run Amps A 643.4 655.5 667.6
Recommended Mains Fuse Size A 670 710 710
Motor Rating kW 20.3 20.3 20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 26.9 26.9 26.9
Unit Nominal Run Amps A 630.1 642.2 654.5
Recommended Mains Fuse Size A 670 670 710
Motor Rating kW 16.8 16.8 16.8
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 33.2 33.2 33.2
Unit Nominal Run Amps A 635.1 647.3 659.5
Recommended Mains Fuse Size A 670 710 710
Motor Rating kW 20.7 20.7 20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet