DeltaChill™ Air Cooled and FreeCool
137
Chiller Technical Manual 7267818 V1.13.0_01_2018
FreeCool
ELECTRICAL DATA 94 95 96 97
Unit Data
DCF092TX-
21HVVV
DCF095TX-
21HVVW
DCF097TX-
21HVWW
DCF099TX-
21HWWW
Nominal Run Amps (1) A 608.0 620.1 632.2 644.4
Maximum Start Amps A 875.4 883.5 895.6 879.8
Recommended Mains Fuse Size A 630 670 670 670
Evaporator
Immersion Heater Rating W 250 250 250 250
Condenser Fan - Per Fan (EC)
Quantity 21 21 21 21
Full Load Amps A 3.9 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6 2.56
Compressor - Per Compressor
Nominal Run Amps A 55.2 / 55.2 / 55.2 55.2 / 55.2 / 59.2 55.2 / 59.2 / 59.2 59.2 / 59.2 / 59.2
Quantity 3 + 3 + 3 3 + 3 + 3 3 + 3 + 3 3 + 3 + 3
Motor Rating kW 33.1 / 33.1 / 33.1 33.1 / 33.1 / 36.2 33.1 / 36.2 / 36.2 36.2 / 36.2 / 36.2
Sump Heater Rating W 140 140 140 140
Start Amps (2) A 326 / 326 / 326 326 / 326 / 298 326 / 298 / 298 298 / 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 564.4 578.0 591.7 605.4
Reactive power reduction/saving (4) kVAr 76.6 74.5 72.4 70.3
Maximum Start Amps A 831.8 841.4 855.1 840.8
Recommended Mains Fuse Size A 630 670 670 670
Electronic Soft-start
Nominal Run Amps A 608.0 620.1 632.2 644.4
Maximum Start Amps A 745.0 753.1 765.2 760.6
Recommended Mains Fuse A 630 670 670 670
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 564.4 578.0 591.7 605.4
Maximum Start Amps A 701.4 711.0 724.7 721.6
Recommended Mains Fuse Size A 630 670 670 670
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 28.5 28.5 28.5 35.0
Unit Nominal Run Amps A 636.4 648.4 660.5 679.1
Recommended Mains Fuse Size A 670 670 710 710
Motor Rating kW 16.4 16.4 16.4 20.3
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 35.0 35.0 35.0 41.5
Unit Nominal Run Amps A 642.9 654.9 667.0 685.6
Recommended Mains Fuse Size A 670 710 710 710
Motor Rating kW 20.3 20.3 20.3 23.9
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 26.9 26.9 26.9 33.2
Unit Nominal Run Amps A 629.5 641.6 653.8 671.2
Recommended Mains Fuse Size A 670 670 710 710
Motor Rating kW 16.8 16.8 16.8 20.7
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 33.2 33.2 33.2 39.2
Unit Nominal Run Amps A 634.5 646.7 658.9 676.0
Recommended Mains Fuse Size A 670 710 710 710
Motor Rating kW 20.7 20.7 20.7 24.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.