Ambient (°C)
Model
Supply
Temp
°C
25°C 30°C 35°C 40°C
Output Input Output Input Output Input Output Input
kW kW kW kW kW kW kW kW
130
DCC074TR-17GPYY
5 757.9 194.4 722.9 214.5 683.6 237.4 639.7 262.9
6 780.4 195.7 744.6 215.9 704.0 238.7 659.4 264.3
7 803.2 197.1 766.7 217.2 724.9 240.0 679.5 265.8
8 826.4 198.5 789.1 218.6 746.6 241.5 700.0 267.2
9 849.7 199.9 811.7 220.0 767.9 242.8 720.7 268.7
10 873.3 201.3 834.6 221.5 790.2 244.3 741.9 270.2
131
DCC079TR-18GYYY
5 817.9 209.3 779.7 230.8 736.9 255.2 689.4 282.3
6 842.4 210.8 803.3 232.3 758.5 256.4 710.8 283.8
7 867.4 212.3 827.4 233.8 781.6 257.9 732.6 285.4
8 892.7 213.8 851.8 235.3 805.0 259.5 754.8 287.0
9 918.3 215.4 876.5 236.9 828.7 261.1 777.3 288.6
10 944.2 217.0 901.5 238.4 852.9 262.7 800.3 290.2
132
DCC082TR-17GYVV
5 847.7 221.1 807.5 244.0 763.2 270.5 714.2 300.2
6 873.3 222.7 832.8 245.8 786.8 272.1 736.3 301.8
7 899.3 224.4 857.8 247.4 810.7 273.8 758.8 303.3
8 925.4 226.0 882.6 248.9 835.1 275.4 781.6 304.9
9 951.9 227.7 908.3 250.6 859.7 277.1 804.9 306.5
10 978.7 229.4 934.4 252.4 884.8 278.9 828.5 308.2
133
DCC085TR-18GVVV
5 868.6 223.5 826.7 246.7 781.4 273.9 731.0 304.5
6 894.8 225.0 853.1 248.6 805.7 275.5 754.0 306.1
7 921.2 226.6 878.7 250.2 830.3 277.1 777.3 307.7
8 948.1 228.2 903.9 251.6 855.3 278.8 801.1 309.4
9 975.3 229.9 930.3 253.3 880.6 280.5 825.3 311.1
10 1002.7 231.6 957.1 255.0 906.3 282.2 849.9 312.8
134
DCC088TR-18GVVW
5 910.2 236.0 866.8 260.6 818.1 288.8 764.7 320.5
6 937.4 237.6 892.8 262.2 843.4 290.5 788.3 322.2
7 965.3 239.4 919.7 263.9 869.2 292.3 812.4 323.9
8 993.7 241.2 947.7 265.9 895.4 294.1 837.0 325.6
9 1022.3 243.1 974.9 267.6 922.0 296.0 861.9 327.3
10 1051.4 244.9 1003.0 269.5 949.0 297.9 887.3 329.1
135
DCC091TR-18GVWW
5 942.7 248.0 898.1 273.7 848.1 303.2 792.8 336.2
6 970.3 249.6 924.9 275.4 874.1 305.0 816.8 337.8
7 998.9 251.5 952.6 277.3 900.5 306.9 841.2 339.5
8 1027.9 253.4 980.8 279.3 927.3 308.9 866.0 341.2
9 1057.2 255.4 1008.9 281.2 954.5 310.8 891.1 343.0
10 1086.8 257.4 1037.6 283.2 982.1 312.9 916.7 344.8
1 Output kW refers to the chilled water duty.
2 Input kW refers to the unit input power (compressor + fans).
3 Duties applicable for chilled water ∆T between 4 and 8°C.
4 Interpolate for water temperatures between those quoted, do not extrapolate.
5 Water ow rate (l/s) = Output ÷ (Cp x ∆T)
6 For conditions outside of those quoted please refer to Airedale.
DCC Performance Data EC Fans