Ambient (°C)
Model
Supply
Temp
°C
25°C 30°C 35°C 40°C
Output Input Output Input Output Input Output Input
kW kW kW kW kW kW kW kW
124
DCC077TR-15GYYY
5 806.1 216.5 769.0 238.6 726.8 263.7 680.6 291.7
6 830.3 218.1 792.3 240.3 749.0 265.4 701.0 293.1
7 855.6 219.9 815.9 241.9 771.6 267.0 721.7 294.5
8 879.9 221.5 839.9 243.6 794.6 268.8 742.7 295.9
9 905.1 223.2 864.3 245.4 818.0 270.5 764.0 297.4
10 930.7 224.9 889.0 247.1 841.7 272.3 785.6 298.9
125
DCC080TR-16GYYV
5 826.9 218.8 788.2 241.3 745.0 267.1 697.4 295.9
6 851.8 220.4 812.6 243.0 767.9 268.7 718.7 297.4
7 877.5 222.2 836.9 244.7 791.2 270.4 740.2 298.9
8 902.6 223.7 861.3 246.3 814.8 272.1 762.1 300.4
9 928.5 225.4 886.3 248.0 838.8 273.8 784.4 301.9
10 954.7 227.2 911.7 249.8 863.2 275.6 807.0 303.5
126
DCC083TR-15GVVV
5 856.2 231.7 816.4 256.0 770.9 283.7 716.3 313.2
6 882.0 233.4 841.3 257.7 794.0 285.2 737.8 314.6
7 908.2 235.2 866.6 259.5 817.3 286.7 759.7 316.2
8 934.7 237.0 892.2 261.3 840.9 288.3 781.9 317.7
9 961.4 238.8 918.1 263.2 864.9 289.9 804.4 319.3
10 988.5 240.7 944.4 265.1 889.1 291.5 827.3 321.0
127
DCC086TR-15GVVW
5 897.0 244.9 853.8 270.0 803.5 298.3 745.7 329.1
6 924.1 246.8 879.5 271.8 827.3 300.0 767.9 330.7
7 951.5 248.8 905.6 273.7 851.5 301.7 790.5 332.5
8 979.4 250.7 932.1 275.6 876.1 303.4 813.5 334.2
9 1007.6 252.7 958.9 277.6 900.9 305.2 836.8 336.0
10 1036.0 254.8 986.1 279.6 926.1 307.1 860.4 337.8
128
DCC088TR-15GVWW
5 929.0 257.5 883.7 283.5 830.0 312.5 770.2 344.7
6 956.8 259.5 909.7 285.3 854.3 314.3 792.8 346.5
7 984.9 261.6 936.1 287.2 878.9 316.2 815.8 348.4
8 1013.3 263.7 962.7 289.2 903.8 318.1 839.1 350.3
9 1042.2 265.8 989.7 291.2 929.1 320.0 862.8 352.2
10 1070.9 267.9 1017.0 293.3 954.6 322.0 886.8 354.2
129
DCC091TR-15GWWW
5 961.1 270.1 913.6 296.9 856.5 326.7 794.7 360.3
6 989.5 272.2 939.9 298.8 881.2 328.7 817.7 362.2
7 1018.2 274.4 966.5 300.8 906.2 330.7 841.1 364.3
8 1047.3 276.6 993.4 302.8 931.6 332.8 864.8 366.3
9 1076.7 278.8 1020.5 304.8 957.2 334.9 888.8 368.4
10 1105.9 281.0 1048.0 306.9 983.1 337.0 913.2 370.6
1 Output kW refers to the chilled water duty.
2 Input kW refers to the unit input power (compressor + fans).
3 Duties applicable for chilled water ∆T between 4 and 8°C.
4 Interpolate for water temperatures between those quoted, do not extrapolate.
5 Water ow rate (l/s) = Output ÷ (Cp x ∆T)
6 For conditions outside of those quoted please refer to Airedale.
DCC Performance Data EC Fans