Ambient (°C)
Model
Supply
Temp
°C
25°C 30°C 35°C 40°C
Output Input Output Input Output Input Output Input
kW kW kW kW kW kW kW kW
118
DCC065DR-14DWW0
5 666.7 168.7 635.4 186.2 599.9 206.1 561.5 228.8
6 686.4 169.9 654.4 187.4 618.0 207.3 578.7 230.1
7 706.2 171.1 672.7 188.4 636.5 208.6 596.2 231.3
8 726.3 172.4 693.1 189.9 655.2 209.9 614.0 232.6
9 746.6 173.7 712.0 191.0 674.1 211.2 632.1 233.9
10 767.2 175.0 732.0 192.3 693.3 212.5 650.5 235.3
119
DCC068TR-13GPPY
5 708.9 188.1 675.7 207.4 638.4 229.4 596.6 253.8
6 729.8 189.4 696.0 208.8 657.8 230.9 614.5 255.1
7 751.2 190.9 716.7 210.3 677.5 232.4 632.5 256.3
8 773.1 192.4 737.6 211.8 697.6 233.9 650.8 257.6
9 794.9 193.9 758.8 213.3 717.8 235.4 669.3 258.9
10 817.1 195.4 780.3 214.8 738.0 236.8 688.1 260.2
120
DCC072TR-14GPYY
5 747.1 201.7 712.5 222.3 673.7 245.9 630.7 272.1
6 768.7 203.0 733.9 223.8 694.2 247.4 649.9 273.5
7 791.2 204.5 755.6 225.3 715.0 248.9 668.9 274.8
8 814.4 206.2 777.6 226.9 736.1 250.5 688.3 276.2
9 837.0 207.6 799.9 228.5 757.5 252.1 707.9 277.5
10 860.2 209.2 822.4 230.1 779.0 253.7 727.8 278.9
121
DCC077TR-13GYYV
5 813.9 228.6 773.3 251.1 726.8 276.6 674.9 304.5
6 838.2 230.4 796.1 252.8 748.1 278.2 694.7 306.1
7 862.9 232.2 819.2 254.5 769.6 279.9 714.8 307.8
8 887.4 233.9 842.6 256.2 791.5 281.6 735.3 309.5
9 912.2 235.6 866.3 258.0 813.6 283.3 756.0 311.2
10 937.2 237.4 890.3 259.9 836.1 285.1 777.1 313.0
122
DCC080TR-14GYVV
5 835.0 230.2 794.9 253.6 748.9 280.1 695.6 308.8
6 860.1 231.9 818.7 255.3 771.0 281.7 716.2 310.4
7 885.5 233.7 842.9 257.0 793.5 283.3 737.2 312.0
8 911.0 235.5 867.4 258.8 816.2 284.9 758.6 313.6
9 936.8 237.2 892.2 260.6 839.3 286.6 780.2 315.3
10 962.9 239.1 917.3 262.5 862.6 288.3 802.2 317.0
123
DCC070TR-16GPPY
5 720.4 180.9 686.5 199.6 648.1 220.8 606.2 244.7
6 741.9 182.1 707.2 200.8 667.7 222.0 625.0 246.1
7 763.7 183.4 728.2 202.1 688.1 223.4 644.1 247.4
8 785.8 184.8 749.6 203.5 708.5 224.7 663.5 248.8
9 808.1 186.1 771.1 204.8 729.0 226.0 683.3 250.2
10 830.7 187.5 793.0 206.2 749.8 227.4 703.4 251.6
1 Output kW refers to the chilled water duty.
2 Input kW refers to the unit input power (compressor + fans).
3 Duties applicable for chilled water ∆T between 4 and 8°C.
4 Interpolate for water temperatures between those quoted, do not extrapolate.
5 Water ow rate (l/s) = Output ÷ (Cp x ∆T)
6 For conditions outside of those quoted please refer to Airedale.