Technic al
Chillers
DeltaChill™ Air Cooled and FreeCool
151
Chiller Technical Manual 7267818 V1.13.0_01_2018
Air Cooled
Ambient (°C)
Model
Supply
Temp
°C
25°C 30°C 35°C 40°C
Output Input Output Input Output Input Output Input
kW kW kW kW kW kW kW kW
148
DCC056DX-12DVV0
5 581.8 149.1 549.8 164.8 514.7 182.7 476.7 202.9
6 598.7 150.2 565.9 165.9 529.8 183.9 490.8 204.0
7 615.9 151.3 582.2 167.0 545.1 185.0 505.0 205.2
8 633.2 152.5 598.6 168.2 560.6 186.2 519.5 206.4
9 650.7 153.6 615.3 169.4 576.3 187.4 534.2 207.7
10 668.4 154.9 632.1 170.7 592.2 188.7 549.0 208.9
149
DCC058DX-12DVW0
5 607.6 161.1 574.0 178.0 537.1 197.4 497.3 219.0
6 624.9 162.3 590.4 179.3 552.5 198.6 511.6 220.3
7 642.4 163.6 607.0 180.6 568.2 200.0 526.1 221.7
8 660.1 164.8 623.8 181.9 584.0 201.3 540.8 223.1
9 677.9 166.1 640.8 183.3 599.9 202.7 555.8 224.5
10 695.9 167.5 657.9 184.6 616.1 204.1 570.9 225.9
150
DCC061DX-12DWW0
5 644.5 173.9 608.0 192.1 568.2 212.7 525.4 235.8
6 662.5 175.3 625.1 193.5 584.2 214.2 540.2 237.4
7 680.8 176.7 642.4 195.0 600.4 215.7 555.2 238.9
8 699.3 178.1 659.8 196.5 616.7 217.3 570.4 240.5
9 717.9 179.6 677.4 198.0 633.3 218.9 585.8 242.1
10 736.6 181.2 695.2 199.6 650.0 220.5 601.4 243.8
151
DCC050DX-14EPV0
5 516.4 124.4 491.6 137.3 463.1 152.1 431.8 168.8
6 531.8 125.2 506.2 138.1 476.9 152.8 444.8 169.5
7 547.3 126.0 520.9 138.8 491.0 153.5 458.0 170.3
8 562.9 126.8 535.8 139.6 505.2 154.3 471.4 171.1
9 578.5 127.6 550.8 140.4 519.5 155.1 485.0 171.9
10 594.2 128.4 566.0 141.2 534.0 155.9 498.8 172.7
152
DCC052DX-14EYY0
5 539.4 135.2 513.0 148.9 483.7 164.5 451.6 182.0
6 555.1 136.0 528.0 149.7 497.9 165.3 464.9 182.9
7 570.9 136.8 543.2 150.5 512.4 166.2 478.5 183.8
8 586.9 137.7 558.6 151.4 527.0 167.1 492.3 184.7
9 603.0 138.5 574.1 152.3 541.8 168.0 506.3 185.6
10 619.1 139.4 589.7 153.2 556.8 168.9 520.5 186.5
153
DCC054DX-13DYV0
5 564.2 141.9 534.9 156.5 502.5 173.2 467.3 192.0
6 580.7 142.8 550.5 157.4 517.3 174.2 481.1 193.0
7 597.3 143.8 566.4 158.4 532.3 175.2 495.1 194.0
8 614.1 144.8 582.5 159.4 547.5 176.2 509.4 195.0
9 631.0 145.8 598.7 160.4 562.9 177.2 523.8 196.1
10 648.1 146.8 615.1 161.5 578.4 178.3 538.5 197.2
154
DCC057DX-14DVV0
5 593.4 145.0 562.3 160.0 527.9 177.3 490.5 196.9
6 611.0 145.9 579.0 161.0 543.7 178.3 505.3 197.9
7 628.7 146.9 595.9 161.9 559.7 179.3 520.2 198.9
8 646.7 147.9 613.1 163.0 575.9 180.3 535.4 199.9
9
664.8 149.0 630.4 164.0 592.4 181.4 550.9 201.0
10 683.1 150.0 648.0 165.1 609.0 182.4 566.5 202.1
1 Output kW refers to the chilled water duty.
2 Input kW refers to the unit input power (compressor + fans).
3 Duties applicable for chilled water ∆T between 4 and 8°C.
4 Interpolate for water temperatures between those quoted, do not extrapolate.
5 Water ow rate (l/s) = Output ÷ (Cp x ∆T)
6 For conditions outside of those quoted please refer to Airedale.
DCC Performance Data EC Fans