Technic al
Chillers
DeltaChill™ Air Cooled and FreeCool
164
Chiller Technical Manual 7267818 V1.13.0_01_2018
Air Cooled
119 120 121
DCC068TR-13GPPY DCC072TR-14GPYY DCC077TR-13GYYV
FreeCooling No No No
Enhance Capital Allowance No No No
Number of Refrigeration Circuits 3 3 3
Cooling Duty - EC Fans
Nominal Output - Mechanical (1) kW 677.5 715.0 769.6
Nominal Input - Mechanical kW 232.4 248.9 279.9
EER (2) 2.92 2.87 2.75
ESEER 4.10 4.13 4.03
Nominal Output - Free Cooling kW N/A N/A N/A
Ambient temperature for
100% Free Cooling
(5) °C N/A N/A N/A
Capacity Steps % 15-30-45-60-75-90-100
15-30-40-55-65-
75-90-100
10-25-35-45-55-
70-80-90-100
Minimum Turndown Ratio 0.16 0.15 0.12
Dimensions (H x W x L) mm 2682 x 2200 x 8242 2682 x 2200 x 8242 2682 x 2200 x 8242
Weight
Machine (3) kg 5900 6120 6290
Operating kg 6510 6725 6925
Water Volume (Total Internal) l 610 605 635
Maximum Waterow l/s 35.9 47.5 46.1
Minimum Waterow l/s 8.4 10.5 17.7
Face Area (Total) 2.38 2.38 2.38
Nominal Airow - EC Fans m³/s 83.8 90.2 83.8
Quantity 13 14 13
Maximum Speed - EC Fans rpm 1026 1026 1026
Compressor
Tandem +
Tandem + Trio
Tandem + Trio + Trio Trio + Trio + Trio
Quantity of Compressors 7 8 9
Oil Charge Volume (Total) l
2 x 5.3 + 2 x 5.3
+ 3 x 5.3
2 x 5.3 + 3 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
Refrigeration R410A / 2088
Charge (Total) kg 24 + 27 + 31 24 + 31 + 31 27 + 29 + 33
GWP Tonnes Equivalent CO2 tCO2 50 + 56 + 65 50 + 65 + 65 56 + 61 + 69
Refrigerant Control Electronic Expansion Valve (EEV)
Water Inlet / Outlet - Unit DN125 DN125 DN150
Water Drain / Bleed - Evap inch 1/2 1/2 1/2
Water System
Minimum System Water Volume (4) l 1887 1875 1534
Maximum System
Operating Pressure
Bar 10 10 10
DCC Mechanical Data - Regular Quiet
(1) Based on units performance at 12/7°C return/supply temperatures, 35°C ambient, 100% water. All performance data supplied in accordance with BBS EN14511-1:2013
(2) EER = DX Cooling Output / (Compressor input power + Fan Input Power),
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options tted please refer to Airedale.
(4) For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations
(5) Ambient temperature that full Freecool capacity can be achieved