122 123 124
DCC080TR-14GYVV DCC070TR-16GPPY DCC077TR-15GYYY
FreeCooling No No No
Enhance Capital Allowance No No No
Number of Refrigeration Circuits 3 3 3
Cooling Duty - EC Fans
Nominal Output - Mechanical (1) kW 793.5 688.1 771.6
Nominal Input - Mechanical kW 283.3 223.4 267.0
EER (2) 2.80 3.08 2.89
ESEER 4.07 4.27 4.16
Nominal Output - Free Cooling kW N/A N/A N/A
Ambient temperature for
100% Free Cooling
(5) °C N/A N/A N/A
Capacity Steps %
10-25-35-45-55-
70-80-90-100
15-30-45-60-75-90-100
10-25-35-45-55-
70-80-90-100
Minimum Turndown Ratio 0.11 0.16 0.12
Dimensions (H x W x L) mm 2682 x 2200 x 8242 2682 x 2200 x 9374 2682 x 2200 x 9374
Weight
Machine (3) kg 6370 6295 6660
Operating kg 7010 6905 7355
Water Volume (Total Internal) l 640 610 695
Maximum Waterow l/s 46.1 35.9 46.1
Minimum Waterow l/s 17.7 8.4 17.7
Face Area (Total) m² 2.38 2.38 2.38
Nominal Airow - EC Fans m³/s 90.2 103.1 96.7
Quantity 14 16 15
Maximum Speed - EC Fans rpm 1026 1026 1026
Compressor Trio + Trio + Trio
Tandem +
Tandem + Trio
Trio + Trio + Trio
Quantity of Compressors 9 7 9
Oil Charge Volume (Total) l
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
2 x 5.3 + 2 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
Refrigeration R410A / 2088
Charge (Total) kg 27 + 33 + 33 28 + 31 + 34 31 + 33 + 33
GWP Tonnes Equivalent CO2 tCO2 56 + 69 + 69 58 + 65 + 71 65 + 69 + 69
Refrigerant Control Electronic Expansion Valve (EEV)
Water Inlet / Outlet - Unit DN150 DN125 DN150
Water Drain / Bleed - Evap inch 1/2 1/2 1/2
Water System
Minimum System Water Volume (4) l 1534 1911 1551
Maximum System
Operating Pressure
Bar 10 10 10
DCC Mechanical Data - Regular Quiet
(1) Based on units performance at 12/7°C return/supply temperatures, 35°C ambient, 100% water. All performance data supplied in accordance with BBS EN14511-1:2013
(2) EER = DX Cooling Output / (Compressor input power + Fan Input Power),
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options tted please refer to Airedale.
(4) For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations
(5) Ambient temperature that full Freecool capacity can be achieved