EasyManua.ls Logo

AIREDALE DeltaChill - Page 166

AIREDALE DeltaChill
302 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technic al
Chillers
DeltaChill™ Air Cooled and FreeCool
166
Chiller Technical Manual 7267818 V1.13.0_01_2018
Air Cooled
125 126 127
DCC080TR-16GYYV DCC083TR-15GVVV DCC086TR-15GVVW
FreeCooling No No No
Enhance Capital Allowance No No No
Number of Refrigeration Circuits 3 3 3
Cooling Duty - EC Fans
Nominal Output - Mechanical (1) kW 791.2 817.3 851.5
Nominal Input - Mechanical kW 270.4 286.7 301.7
EER (2) 2.93 2.85 2.82
ESEER 4.18 4.13 4.20
Nominal Output - Free Cooling kW N/A N/A N/A
Ambient temperature for
100% Free Cooling
(5) °C N/A N/A N/A
Capacity Steps %
10-25-35-45-55-
70-80-90-100
10-25-35-45-55-
70-80-90-100
10-25-35-45-55-
70-80-90-100
Minimum Turndown Ratio 0.11 0.12 0.11
Dimensions (H x W x L) mm 2682 x 2200 x 9374 2682 x 2200 x 9374 2682 x 2200 x 9374
Weight
Machine (3) kg 6740 6725 6775
Operating kg 7435 7415 7460
Water Volume (Total Internal) l 695 690 685
Maximum Waterow l/s 46.1 46.1 63.1
Minimum Waterow l/s 17.7 17.7 14.1
Face Area (Total) 2.38 2.38 2.38
Nominal Airow - EC Fans m³/s 103.1 96.7 96.7
Quantity 16 15 15
Maximum Speed - EC Fans rpm 1026 1026 1026
Compressor Trio + Trio + Trio Trio + Trio + Trio Trio + Trio + Trio
Quantity of Compressors 9 9 9
Oil Charge Volume (Total) l
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
Refrigeration R410A / 2088
Charge (Total) kg 30 + 33 + 37 31 + 33 + 34 33 + 35 + 35
GWP Tonnes Equivalent CO2 tCO2 63 + 69 + 77 65 + 69 + 71 69 + 73 + 73
Refrigerant Control Electronic Expansion Valve (EEV)
Water Inlet / Outlet - Unit DN150 DN150 DN150
Water Drain / Bleed - Evap inch 1/2 1/2 1/2
Water System
Minimum System Water Volume (4) l 1551 1645 1661
Maximum System
Operating Pressure
Bar 10 10 10
DCC Mechanical Data - Regular Quiet
(1) Based on units performance at 12/7°C return/supply temperatures, 35°C ambient, 100% water. All performance data supplied in accordance with BBS EN14511-1:2013
(2) EER = DX Cooling Output / (Compressor input power + Fan Input Power),
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options tted please refer to Airedale.
(4) For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations
(5) Ambient temperature that full Freecool capacity can be achieved

Table of Contents