73 74 75
DCF075TX-14GPYY DCF059DX-15DYV0 DCF061DX-16DVV0
FreeCooling Yes Yes Yes
Enhance Capital Allowance No No No
Number of Refrigeration Circuits 3 2 2
Cooling Duty - EC Fans
Nominal Output - Mechanical (1) kW 737.6 577.7 599.6
Nominal Input - Mechanical kW 262.2 176.8 180.9
EER (2) 2.81 3.27 3.31
ESEER 3.93 4.29 4.33
Nominal Output - Free Cooling kW 530.1 512.6 540.7
Ambient temperature for
100% Free Cooling
(5) °C -1.7 1.4 1.6
Capacity Steps %
15-30-45-55-70-
80-90-100
15-35-50-70-85-100 20-35-50-70-85-100
Minimum Turndown Ratio 0.16 0.17 0.18
Dimensions (H x W x L) mm 2682 x 2200 x 8242 2682 x 2200 x 9374 2682 x 2200 x 9374
Weight
Machine (3) kg 7400 6885 6995
Operating kg 8660 7970 8105
Water Volume (Total Internal) l 1260 1085 1110
Maximum Waterow l/s 46.1 46.7 46.7
Minimum Waterow l/s 17.7 10.7 10.7
Face Area (Total) m² 2.38 2.38 2.38
Nominal Airow - EC Fans m³/s 56.0 60.0 64.0
Quantity 14 15 16
Maximum Speed - EC Fans rpm 725 725 725
Compressor Tandem + Trio + Trio Trio + Trio Trio + Trio
Quantity of Compressors 8 6 6
Oil Charge Volume (Total) l
2 x 5.3 + 3 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3 3 x 5.3 + 3 x 5.3
Refrigeration R410A / 2088
Charge (Total) kg 27 + 34 + 34 39 + 42 44 + 42
GWP Tonnes Equivalent CO
2
tCO2 56 + 71 + 71 81 + 88 92 + 88
Refrigerant Control Electronic Expansion Valve (EEV)
Water Inlet / Outlet - Unit DN150 DN125 DN125
Water Drain / Bleed - Evap inch 1/2 1/2 1/2
Water System
Minimum System Water Volume (4) l 2181 1800 1922
Maximum System
Operating Pressure
Bar 10 10 10
(1) Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
All performance data supplied in accordance with BBS EN14511-1:2013
(2) EER = DX Cooling Output / (Compressor input power + Fan Input Power),
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options tted please refer to Airedale.
(4) For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations
(5) Ambient temperature that full Freecool capacity can be achieved
DCF Mechanical Data Extra Quiet