Parameter Lists
88
890053-00-02
Code
Name
LCD Display
Setting Range
Initial value
Property*
Ref.
33
Jump frequency upper limit3
Jump Hi 3
Jump frequency lower
limit3- Maximum frequency
(Hz)
35.00
O
41
8
Brake Open Current
BR Rls Curr
0.0 - 180.0%
50.00
p.147
42
Brake Open Delay Time
BR Rls Dly
0.0 - 10.0 (sec)
1.00
44
Brake Open Forward
Frequency
BR Rls Fwd Fr
0 - Maximum Frequency
1.00
45
Brake Open Reverse
Frequency
BR Rls Rev Fr
0 - Maximum Frequency
1.00
p.147
46
Brake Close Delay Time
BR Eng Dly
0.0 - 10.0 (sec)
1.00
47
Brake Close Frequency
BR Eng Fr
0 - Maximum Frequency
2.00
50
Energy saving operation
E-Save Mode
0
None
0
None
Δ
p.151
1
Manual
2
Auto
51
9
Energy saving level
Energy Save
030 (%)
0
O
p.151
52
Energy saving point search
time
E-Save Det T
0.0-100.0 (sec)
20.0
Δ
64
Cooling fan control
Fan Control
0
During Run
0
During Run
O
p.152
1
Always ON
2
Temp Control
74
Selection of regeneration
evasion function for press
RegenAvd Sel
0
No
0
No
Δ
p.153
1
Yes
75
Voltage level of regeneration
evasion motion for press
RegenAvd Level
240V: 300-400 V
350
Δ
480V: 600-800 V
700
575V: 800-980V
870
76
10
Compensation frequency
limit of regeneration evasion
for press
CompFreq Limit
0.00-60.00 Hz
1.00
Δ
p.153
77
Regeneration evasion for
press, P- Gain
RegenAvd Pgain
240V,
480V
0.0-100.0%
50.0
O
575V
0.0-200.0%
100.0
78
Regeneration evasion for
press, I gain
RegenAvd Igain
2030000 (msec)
500
O
[1] ADV-0304 are displayed when ADV-01 is set to ‘1 (S-curve)’.
[2] ADV-0506 are displayed when ADV-02 is set to ‘1 (S-curve)’.
[3] ADV-11 is displayed when ADV-10 is set to ‘1 (Yes)’.
[4] ADV-12 and 13 are displayed when ADV-07 is set to ‘1 (DC-Start)'.
[5] ADV-14 - 17 are displayed when ADV-08 is set to ‘1 (DC-Brake)’.
[6] ADV-25 and 26 are displayed when ADV-24 is set to '1' (Yes)
[7] ADV-2833 are displayed when ADV-27 is set to ‘1 (Yes)’.
[8] ADV-41 - 47 are displayed if either OUT-31 ~ 36 are set to 42 (BR Control).
[9] ADV-51 is displayed when ADV-50 is set to ‘1 (Manual)’. ADV-52 is displayed when ADV-50 is set to ‘2 (Auto)’.
[10] ADV-7678 are displayed when ADV-74 is set to ‘1 (Yes)’.