8.1 Application Group 2 (AP2)
Application Group 2 includes additional pump and fan related parameters. These are Pump Load
Curve Tuning, Pump Clean Operation, Check Valve timing, Damper status monitoring, Oil Pump
starter control and Motor Pre-Heat function.
8.1.1 AP2 Parameter List
Code
Name
LCD
Display
Setting Range
Initial
Value
Property*
Ref.
00
Jump Code
Jump Code
199
40
O
p.74
01
1
Load curve Tuning
Load Tune
0
No
0
No
Δ
p.257
1
Yes
02
Load Curve - Low Freq
Load Fit Lfreq
Base Freq*15%Load Fit Hfreq
(AP2-08)
30.00
Δ
p.257
03
Current at Low Freq
Load Fit LCurr
0.080.0 (%)
40.0
Δ
p.257
04
Power at Low Freq
Load Fit LPwr
0.080.0 (%)
30.0
Δ
p.257
08
Load Curve - High Freq
Load Fit HFreq
Load Fit LFreq HighFreq
51.00
Δ
p.257
09
Current at High Freq
Load Fit HCurr
Load Fit LCurr 200.0 (%)
80.0
Δ
p.257
10
Power at High Freq
Load Fit HPwr
Load Fit LPwr 200.0 (%)
80.0
Δ
p.257
11
Load curve - Current
Load Curve Cur
-
-
X
p.257
12
Load curve - Power
Load Curve Pwr
-
-
X
p.257
15
Pump clean setting 1
Pump Clean
Mode1
0
None
0
None
O
p.259
1
DI Dependent
2
Output Power
3
Output Current
16
Pump clean setting2
Pump Clean
Mode2
0
None
0
None
Δ
p.259
1
Start
2
Stop
3
Start and Stop
17
Pump clean load setting
PC Curve Rate
0.1200.0 (%)
100.0
O
p.259
18
Pump clean reference band
PC Curve Band
0.0100.0 (%)
5.0
O
p.259
19
Pump clean operation delay time
PC Curve DT
0.06000.0 (sec)
60.0
O
p.259
20
Pump clean start delay time
PC Start DT
0.06000.0 (sec)
10.0
O
p.259
21
0 speed operating time at Fx/Rx
switching
PC Step DT
0.16000.0 (sec)
5.0
O
p.259
22
Pump clean Acc time
PC Acc Time
0.0600.0 (sec)
10.0
O
p.259
23
Pump clean Dec time
PC Dec Time
0.0600.0 (sec)
10.0
O
p.259
24
Forward step maintaining time
Fwd SteadyTime
0.0600.0 (sec)
10.0
O
p.259
25
Forward step maintaining
frequency
Fwd SteadyFreq
0.00, Low Freq High Freq
30.00
O
p.259
26
Reverse step running time
Rev SteadyTime
0.0600.0 (sec)
10.0
O
p.259
27
Reverse step running frequency
Rev SteadyFreq
0.00, Low Freq High Freq
30.00
O
p.259
28
Pump clean number of Fx/Rx
steps
PC Num of Steps
110
2
O
p.259
29
Pump clean function cycle
monitoring
Repeat Num Mon
-
-
X
p.259
30
Number of pump clean repetitions
Repeat Num Set
010
2
O
p.259
31
Operation after pump clean end
PC End Mode
0
Stop
0
Stop
Δ
p.259
1
Run
32
Pump clean continuous limit time
PC Limit Time
660 (min)
10
O
p.259
33
Pump clean continuous limit
numbers
PC Limit Num
010
3
O
p.259
38
Dec Valve operation frequency
Dec Valve Freq
Low Freq High Freq
40.00
O
p.263
39
Dev Valve Dec time
Dev Valve Time
0.06000.0 (sec)
0.0
O
p.263
40
Start and End ramp settings
Start&End Ramp
0
No
0
No
Δ
p.264