Parameter Descriptions
102
890053-00-02
5.1.2 DRV-03, DRV-04 Acceleration and Deceleration Times
5.1.2.1 Acc/Dec Time Based on Maximum Frequency
Acc/Dec times are based on maximum frequency (BAS-08 set to 0, MaxFreq). Acceleration time set at
DRV-03 (Acceleration time) refers to the time required for the inverter to reach the maximum frequency
from a stopped (0 Hz) state. Likewise, deceleration time set at DRV-04 refers to the time required to
decelerate from the maximum frequency to a stopped state (0 Hz).
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV
03
Acceleration
time
Acc Time
20.0
240V:7.5~60HP
0.0600.0
sec
480V,575V:
7.5~125HP
60.0
240V: 75~125HP
480V: 150~400HP
100.0
480V: 500~800HP
04
Deceleration
time
Dec Time
30.0
240V:7.5~60HP
0.0600.0
sec
480V,575V:
7.5~125HP
90.0
240V: 75~125HP
480V: 150~400HP
150.0
480V: 500~800HP
20
Maximum
frequency
Max Freq
60.00
40.00400.00
Hz
BAS
08
Acc/Dec
reference
frequency
Ramp T
Mode
0
Max Freq
01
-
09
Time scale
Time scale
1
0.1 sec
02
-
Acc/Dec Time Based on Maximum Frequency Setting Details
Code
Description
BAS-08
Ramp T Mode
Set the parameter value to 0 (Max Freq) to setup Acc/Dec time based on
maximum frequency.
Configuration
Description
0
Max Freq
Set the Acc/Dec time based on maximum frequency.
1
Delta Freq
Set the Acc/Dec time based on operating frequency.
Example: Maximum frequency is 60.00 Hz, the Acc/Dec times are set to 5
seconds, and the frequency reference for operation is set at 30 Hz (half of
60 Hz), the time required to reach 30 Hz therefore is 2.5 seconds (half of 5
seconds).