Preparing the Installation
1.5 Cable Selection
Use cables that meet the required specification for the safe and reliable operation of the product. Refer to
NEC Articles 430.2 and 430.6 along with Table 310-16 for selecting the correct wire sizing. Some local codes
may take precedence over the NEC. Refer to the following information to assist you with cable selection.
Ground Cable and Power Cable Specifications
Wherever possible, use cables with the largest cross-sectional area for mains power wiring to
ensure that voltage drop does not exceed 2%.
Use copper cables rated for 600 V, 75⁰ for power terminal wiring.
Use copper cables rated for 300 V, 75⁰ for control terminal wiring.
The inverters must be grounded with fixed connections.
The minimum size of the protective ground conductor shall comply with the local safety
regulations for high protective grounding.