A protective function operates when under load level condition explained
above is maintained for the warning time set.
Sets the inverter operation mode for situations when an under-load trip
occurs. If set to ‘1 (Free-Run)’, the output is blocked in an under-load fault
event. If set to ‘2 (Dec)’, the inverter decelerates the motor and stops when an
under-load fault occurs.
A protective function operates when under load level conditions explained
above are maintained for the trip time set.
5.8.7 PRT-31 No Motor Trip
The inverter can detect a low motor current condition and will trip on “No Motor trip” if the output
current is below the PRT-32 detection level for the PRT-33 detection time. The inverter responds
to a no motor trip condition when PRT-31 (No Motor detection) is set to ‘1 (Free-Run)’. PRT-31
may be set to (0) None (default) for testing with no motor connected.
Operation for no
motor trip
No motor trip
current level
No Motor Trip Setting Details
PRT-32
No Motor Level
PRT-33
No Motor Time
If the output current value [based on the rated current (MOT-05)] is
lower than the value set at PRT-32 (No Motor Level), and if this
continues for the time set at PRT-33 (No Motor Time), a ‘no motor trip’
occurs.
If BAS-07 (V/F Pattern) is set to ‘1 (Square)’, set PRT-32 (No Motor Level) to a value lower than the
factory default. Otherwise, a ‘no motor trip,’ may occur due to a lack of output current
To operate under load trip properly, a load tuning (AP2-01 Load Tune) must be performed in
advance. If you cannot perform a load tuning, manually set the load fit frequencies (AP2-02 Load Fit
Lfreq–AP2-10 Load Fit Hfreq). The Under Load protection does not operate while the Energy Save
function is in operation.