5.4.5 ADV-10 Power-on Run
The inverter can be set to start operating (output power to the motor) as soon as the inverter powers
up or with some delay time. See caution below. If DRV-06 is set to Keypad, Power-on Run does not
function. In AUTO mode, the inverter starts operating at power-on when the following conditions are met.
With command source set to terminal block (Fx/Rx-1 or Fx/Rx-2).
When ADV-10, Power-on Run is set to Yes with optional delay time.
and a run command remains enabled.
The inverter will start immediately upon power up. Parameter DRV-06 (command source) must be set
to 1 (Fx/Rx-1) or 2 (Fx/Rx-2) along with an active run command.
Power-on Run and Communications (Int 485 or other Field Bus).
With DRV-06 set to ‘3 (Int 485)’ or ‘4 (Field Bus)’ for communications, set COM-96 (PowerOn Resume) to
‘YES’. If the power input to the inverter is cut off due to a power interruption, the inverter memorizes the
run command, frequency reference, and the acc/dec time settings at the time of power interruption. With
COM-96 (PowerOn Resume) set to ‘Yes’, the inverter starts operating based on these settings as soon as
the power supply resumes.